Specifications

Alarm
Alarm wires connect to pins 4 and 5 of the gray
5-pin connector.
Pin Color Designation
4 N/A Alarm Return
5 N/A Alarm input (3.5mA sink)
Connect additional alarm inputs, if required, to
the blue 4-pin connector.
Pin Color Designation
1 N/A Alarm input (3.5mA sink)
2 N/A Alarm input (3.5mA sink)
3 N/A Alarm input (3.5mA sink)
4 N/A Alarm Return
Relay Outputs
Connect relay outputs to pins 1, 2, and 3 of the
gray 5-pin connector.
Pin Color Description
1 N/A Normally Closed
2 N/A Common
3 N/A Normally Open (3.5mA sink)
2. Apply Teflon tape around housing pipe
threads and attach the housing to the outdoor
mounting structure. See instructions supplied
with the structure.
3. Apply power to the housing.
4. On the environmental PC board shown below:
a. Press and hold switch SW2 and observe
green (ac power) and yellow (comm.)
LEDs. The green LED glows steadily and
the yellow LED glows steadily (for RS422)
or blinks (for SensorNet).
b. For RS422 data, press and hold data test
switch SW1 and observe the nearby red
and green LEDs for the following:
Constant green,
Blinking red
RS422 line is
correctly wired.
Constant green,
No red
RS422 “Data In –” is
shorted to ground.
Constant red,
Blinking green
“Data In + /–” wires
are reversed.
Blinking red,
Green off
“Data In +” is
shorted to ground.
Both LEDs off “Data In +/–” wires
are shorted or open.
SW2
LEDs
SW1
RHODUL-03VR/-04VR SPEEDDOME ULTRA VANDAL-RESISTANT OUTDOOR HOUSING 8200-0184-11, REV. A
INSTALLATION AND SERVICE GUIDE
6 of 14