SECURITY CAMERA SYSTEM UPGRADE AND REPLACEMENT
FOR MONTGOMERY COUNTY DETENTION CENTER
SECURITY CAMERA SYSTEM 17000-79
11. A DirectSet menu must be used to provide easy access to common dome
settings when installed with compatible controllers. This DirectSet menu
must provide access to the following features:
a. dome configuration menu
b. auto iris/autofocus resume
c. flip
d. default apple peel pattern
e. set North position
f. line lock off
g. line lock on
h. activate smooth scan
i. activate stepped scan
j. activate random scan
k. activate a preset sequence
l. display the dome information screen
12. Password protection must be provided to prevent unauthorized access.
13. Dome direction indicators and azimuth reading; Dome, Area, Preset,
Pattern, Preset Sequence and alarm names; and zoom, focus, and iris
status must be displayable on the monitor. All on-screen text character
attributes must be user-selectable solid or translucent white, with or
without black outline.
14. On-screen display of dome usage statistics must be available. This usage
information must provide a record of the number of pan, tilt, and zoom
commands issued by the dome; operating time, time from last reset in
seconds, and total reset count.
15. The dome assembly design shall contain four alarm inputs and be field
programmable to receive “normally open” or “normally closed” contacts.
If operating on a SensorNet or RS-422 network, the dome shall be
capable of receiving the alarm and transmitting the alarm back to the
switching system and/or reacting to the alarm event independent of the
switching system. If operating on a Manchester network, the dome must
be able to process the alarm internally and automatically activate a Preset,
Pattern, or Preset Sequence.
16. The dome assembly shall contain a single auxiliary output (outdoor dome)
or three independent auxiliary outputs (indoor dome). The outdoor dome
single auxiliary output shall be a form C relay contact. Each open
collector output must respond as momentary or latching (depending on
system capability).
17. The open collector of each auxiliary shall be required to handle +12Vdc
at a maximum of 40mA.