Specifications

SECURITY CAMERA SYSTEM UPGRADE AND REPLACEMENT
FOR MONTGOMERY COUNTY DETENTION CENTER
SECURITY CAMERA SYSTEM 17000-40
b. INSTANT AUTOCLEAR (alarm clears when alarm input clears
or when manually acknowledged from a system keyboard)
c. INSTANT AUTOCLEAR/NO MANUAL ACKNOWLEDGE
(alarm clears when alarm input clears only)
d. AUTOCLEAR (alarm clears approximately 20 seconds after alarm
input clears or when manually acknowledged from a system
keyboard)
e. AUTOCLEAR/NO MANUAL ACKNOWLEDGE (alarm clears
approximately 20 seconds after alarm input clears only)
5. During alarm response, the matrix switching system must provide
programming for automatic call-up of a camera preset, turn on or off an
auxiliary, and provide on-screen text indicating the occurrence of an
alarm.
6. The system shall provide 128 alarm text messages that can be defined
with 25 alarm display/clearance modes, and 16 e-mail messages.
O. Activity Logging: The system shall have activity logging and reporting to an IP
network PC used for setup and file storage.
P. Tours:
1. The matrix switching system shall support an individual monitor tour
(sequence) for each video output. The monitor tour shall consist of up to
64 entries. Each entry may have an associated video input and dwell time.
2. The matrix switching system shall also support up to 64 system tours.
Each universal tour shall consist of up to 64 entries. Each entry may have
an associated video input, preset, and/or auxiliary action.
3. Video inputs may be included multiple times in the same tour.
Alternatively, a salvo or tour can be substituted for the video input
number to allow sequences of more than 64 entries.
4. The operator must be able to manually step through the tour, stop the
tour or run the tour forward or in reverse.
5. All tour information will reside in non-volatile memory. Tours may also
be called automatically via a programmable seven-day timer. A minimum
of thirty-five user-programmable time slots, independently programmable
for each of seven days, must be provided.