Specifications

SECURITY CAMERA SYSTEM UPGRADE AND REPLACEMENT
FOR MONTGOMERY COUNTY DETENTION CENTER
SECURITY CAMERA SYSTEM 17000-26
intercoms. Additionally, the eight existing projects will need to
be modification to work with and support the new cameras and
system changes where required. All existing Wonderware/Touch
Screen projects must be upgraded to new PC’s running Windows
XP Pro.
b. All projects in the blocks will have to be modified that display the
new CCTV system cameras.
c. Unique screens will have to be created showing the new cameras
and floor plan graphics of the new areas of the facility being
monitored.
d. New screens will also have to be added to both Main Control
Room projects to allow them to display all of the new CCTV
cameras.
e. New floor plan graphics must be added to the Main Control Room
Wonderware projects to display the new CCTV cameras.
2. 4 new projects will need to be created.
a. One (1) on the second floor POD A
b. One (1) on the second floor POD B
c. One (1) on the fourth floor POD C
d. One (1) on the fourth floor POD D
e. Each new project must display the floor plan graphics for the area
it is monitoring.
f. Each new project must display the icons for any doors and
intercoms that will be activated and/or monitored by that specific
HMI workstation.
g. The new HMI Wonderware touch screen projects will be
integrated into the complete Wonderware/touch screen/PLC
network that is currently operating in the facility.
h. The new HMI Wonderware touch screen projects will control
camera call-up by using the existing PLC to command the CCTV
matrix switch.
i. Communicates to the existing PLC will be over Ethernet.
3. Definitions:
a. "Control Panel" shall refer to any type of operator control station,
whether a video monitor or a metallic panel with mechanical
switches.
b. "Switch" shall refer to any mechanical device or video icon used
for making, breaking, or changing the connections in an electrical
control circuit.