Unit installation
TYPICAL SYSTEM CONNECTIONS
Cascading Multiple AD2096A Units
AD2096A
AD2096A
6003-0047-02
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
TERMINAL BOX 2113-0019-01
BROWN
(GRD)
GREEN
RED
GREEN
BROWN
(GRD)
RED
TERMINAL BOX 2113-0019-01
TYPICAL CONNECTIONS TO CASCADE MULTIPLE AD2096A UNITS:
WHEN THE UNITS ARE LESS THAN 7' APART, USE MODULAR CABLE 6003-0047-02
WHEN DISTANCES EXCEED 7', TERMINAL BOXES MUST BE USED
NOTE: FOR DISTANCES GREATER THAN 7' BETWEEN UNITS,
TERMINAL BOXES MUST BE USED. THE MAXIMUM
DISTANCE BETWEEN THE BOXES IS 1000' (330m)
USING SHIELDED, 18 AWG CABLE.
Connection to next cascaded AD2096A AIU,
or to Matrix Switching System
C-6
CABLE 6003-0047-02
FOR DIRECT CONNECTIONS
UP TO 7 FEET