Technical data
Optional Factory-Installed Features—Evaporator/Chilled Water and Condensing Units
Liebert
®
DataMate
™
4
3.0 OPTIONAL FACTORY-INSTALLED FEATURES—EVAPORATOR/CHILLED WATER
AND CONDENSING UNITS
3.1 Electric Reheat
Electric low watt tubular reheat element with non-corrosive metal sheath provides one stage of
non-ionizing reheat to maintain room dry bulb temperature.
3.2 Humidifier/Electric Reheat Package
The humidifier and electric reheat are available as a package for complete humidity control. The
canister humidifier includes a steam-generating type humidifier with automatic flushing circuit, inlet
strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem alarm
annunciates at the wall-mounted display panel. Maximum humidifier water supply pressure is
150psi (1034kPa).
3.3 Optional Configurations—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
• High ambient models for providing catalog capacities at ambient temperatures up to
105°F (40°C): 2- and 3-ton models only.
•Liebert Quiet-Line
™
models for low noise level conditions (below 58 dBA) and for providing
catalog capacities at ambient temperatures up to 95°F (35°C).
• Condenser coils can be phenolic-coated for extended coil life in coastal areas.
3.4 Optional Configurations—Indoor Remote Water/Glycol Condensing Units
Indoor Remote Water/Glycol Condensing Units are also available with the following piping options:
• Two-way water regulating valve with 350psi (2413kPa) design pressure
• Three-way water regulating valve with 150psi (1034kPa) design pressure
• Three-way water regulating valve with 350psi (2413kPa) design pressure