Technical data

Water/Glycol Systems—Capacities and Dimensions
Liebert
®
DataMate
20
Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules
Table 13 Net weight, indoor water/glycol-cooled condensing unit
Model Numbers
Weight
lb (kg)60Hz 50Hz
MC*26W — 175 (79)
MC*38W MC*37W 220 (100)
Source: DPN000208, Rev. 4
Holes for Module
Rigging (typ. 2 each end)
7/8" (22mm) Dia.
Electrical Entrance
for High Voltage
Connection
DPN000208
Rev. 4
PIPING CONNECTIONS
7/8" (22mm) Dia. Electrical
Entrance for Low-Voltage
Connection
7/8" (22.2mm) OD CU
Water/Glycol Outlet Connection
Extends 3-1/2" (88.9mm)
beyond panel exterior
7/8" (22.2mm) OD CU
Water/Glycol Inlet Connection
Extends 3-1/2" (88.9mm)
beyond panel exterior
Suction Line
Male Quick
Connect
Liquid Line
Male Quick
Connect
14" (356mm)
Overall Cabinet
Dimension
8-7/8" (225mm)
50-1/4" (1276mm)
Overall Dimension
48-1/4" (1225mm)
Threaded Rod Centers
46-1/2" (1181mm)
20-3/4"
(527mm)
Minimum Clearance
33" (838mm) This Side
for Component Access
and Removal
Customer Supplied
Threaded Rods for Module
Support from Ceiling (typ. 4)
Outlet
Inlet
Note: Unit is Spaced Evenly in
Reference to Threaded Rod Centers
DIMENSIONAL DATA
Integral Hanging Bracket
12" (305mm)
Threaded Rod
Centers
22-1/2" (572mm)
Cabinet Dimension
3-7/8" (98mm)
8-7/16" (214mm)
Cabinet Dimension