Technical data
Water/Glycol Systems—Capacities and Dimensions
Liebert
®
DataMate
™
18
Figure 10 Dimensions and piping, close-coupled water/glycol condensing unit
Note: Do Not remove evaporator
end panel from panel assembly when
installing internal water/glycol
condensing unit
Piping Access
Plate in
Evaporator
End Panel
A - Liquid Refrigerant Line
Quick Connect Male
Coupling
B - Suction Refrigerant Line
Quick Connect Male
Coupling
D - Return
Leaving
Condenser
Water/Glycol
C - Supply
Entering
Condenser
Water/glycol
Removable
Panels
Outline of
Evaporator
Module
Piping and Electrical
Knockouts
Located on Bottom
and on Back of Unit
Piping and Electrical Knockouts
Located on Bottom and on
Back of Unit
DPN000270
Rev. 2
DPN000269
Rev. 0
14"
(356mm)
Access Panel
(Removable)
Unit Dimensions
Access Panel
(Removable)
Access Panel
(Removable)
12" (305mm)
Condensing
Unit
Shaded area indicates a recommended
clearance of 34" (864mm) in front
of the unit and 12" (305mm) on
the left side for component access and
removal. Minimum clearance is 1" (25mm)
on left side and 18" (457mm) in front.
Floor
Liebert
DataMate
Evaporator
32"
(813mm)
14"
(356mm)