Technical data

Air-Cooled Systems—Capacities and Dimensions
11 Liebert
®
DataMate
Figure 4 Dimensions, evaporator unit
Table 3 Evaporator section dimensions—air-cooled applications
Model
Weight
lb (kg)
Width - A
in. (mm)
Depth
in. (mm)
Height
in. (mm)
DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813)
DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813)
DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813)
Source: DPN000262, Rev. 0
Table 4 Evaporator unit refrigerant connections—pipe size/coupling number
Model Liquid Line A Suction Line B
DME020E 3/8" / #6 1/2" / #11
DME027E 3/8" / #6 7/8" / #11
DME037E 3/8" / #6 7/8" / #11
Grilles are reversible
to allow air direction changes
as shown by the arrows
Cabinet
Outline
5/8"
(16mm)
3-1/2"
(89mm)
1"
(25mm)
10-7/8"
(276mm)
Shaded area indicates a
recommended clearance
of 34" (864mm) in front
of the unit.
Standard Refrigeration and Chilled
Water Piping Opening
Removable Access
Panel
A
32"
(813mm)
Air
Inlet
Air Outlet
A
DPN000262
Rev. 0
FLOOR CUTOUT
DIMENSIONS
for Raised-Floor Piping
See Table 3 for Dimension A