Technical data
Air-Cooled Systems—Capacities and Dimensions
Liebert
®
DataMate
™
8
6.0 AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS
Table 1 60Hz capacities & typical specifications, air-cooled applications
Evaporator Model
DME020E DME027E DME037E
Condensing Unit Type
PFH - Outdoor PFH - Outdoor MCD - Indoor PFH - Outdoor MCD - Indoor
DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C
WB) 38 %RH
Total 5.50 (18,800) 7.20 (24,500) 6.90 (23,600) 10.25 (35,000) 9.70 (33,100)
Sensible 5.50 (18,800) 7.20 (24,500) 6.90 (23,600) 9.95 (33,900) 9.60 (32,800)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C
WB) 45 %RH
Total 5.10 (17,400) 6.70 (22,800) 6.45 (22,000) 9.80 (33,500) 9.25 (31,600)
Sensible 5.05 (17,200) 6.65 (22,700) 6.40 (21,900) 8.90 (30,300) 8.60 (29,400)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C
WB) 50 %RH
Total 4.90 (16,700) 6.40 (21,900) 6.20 (21,100) 9.60 (32,700) 9.05 (30,900)
Sensible 4.70 (16,000) 6.20 (21,100) 6.05 (20,600) 8.20 (28,000) 7.95 (27,100)
Fan Data - Evaporator
CFM (CMH) - High Speed 870 (1478) 1230 (2090)
1320 (2243)
CFM (CMH) - Low Speed 750 (1274) 1050 (1784)
1175(1996
)
Fan Motor hp (W) 0.16 (120) 0.20 (150)*
0.27 (200)**
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
) 2.44 (0.23) 3.92 (0.36)
3.92 (0.36)
Coil Rows 4 3
4
Max Face Velocity-fpm (m/s) 356 (1.8) 313 (1.6)
336 (1.7)
Unit Refrigerant Charge, oz. (kg) 4 (0.11) 5 (0.14)
6.5 (0.18)
Unit Operating Weight, lb. (kg) 230 (104) 330 (150)
365 (165)
Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)
Input Voltage 230-1-60 2.7 (9215) 5.3 (18080)
5.5 (18765)
Humidifier Data - Steam Generator Type
Steam capacity - lb/hr (kg/hr) 3 (1.4) 3 (1.4) 3 (1.4)
Electrical Input Power - kW 1 1 1
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip
Coupling Size, - #6 Female
3/8" 3/8" 3/8"
Suction Line Diameter - Aeroquip
Coupling Size, #11 Female
1/2" 7/8" 7/8"
Humidifier Supply,
OD Cu Compression Fitting
1/4" 1/4" 1/4"
Humidifier Drain, Barb Fitting 1/2" 1/2" 1/2"
Evaporator Drain, Barb Fitting 3/4" 3/4" 3/4"
Filter Washable Polypropylene/Aluminum, MERV4
Condensing Unit Model Number
PFH020A-_L7 PFH027A-_L7 MCD24AL_H7 PFH037A-_L7
MCD36AL_H7
Condensing Unit Rating Conditions 95°F (35°C) Ambient
Coil Face Area ft
2
(m
2
) 4.1 (0.38) 4.1 (0.38) 4.6 (0.43) 7.7 (0.72)
4.6 (0.43)
Rows of Coil 2 2 4 2
4
CFM (CMH) 2200 (3738) 2200 (3738) 1000 (1699) 3000 (5097)
1430 (2490)
Motor, hp (W) 0.20 (149) 0.20 (149) 0.33 (246) 0.20 (149)
0.5 (373)
External Static Pressure, in wg.
(mm)
N/A N/A 0.50 (13) N/A
0.50 (13)
Condensing Unit Refrigerant
Charge, oz. (kg)
134 (3.8) 134 (3.8) 134 (3.8) 213 (6.0) 213 (6.0)
Unit Operating Weight, lb. (kg) 200 (91) 351 (159) 449 (204) 351 (159)
449 (204)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard
rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* DME027 has two motors - 0.08 & 0.12 HP
** DME037 has two motors - 0.11 & 0.16 HP