Instruction Manual
SK-ACP Installation & Operating Manual
B-2
PHYSICAL
Depth 3.0” (7.62 cm)
Width 10.0” (25.40 cm)
Height 11.0” (27.94 cm)
Weight 68.8 oz (1.95 kg)
Housing Material is All Steel; Color is Beige
POWER REQUIREMENTS 16.5-24 VAC, 20 VA or 16-30 VDC, 100 mA plus reader current draw
Power Supply Sold Separately
* A 12 VDC Power Supply may be used if connected to Battery Back-Up Leads.
BACK-UP BATTERY 12 V, 1.2 - 6 Ah (Optional, Sold Separately)
CARD READERS Connect two card readers with two-line Wiegand output, up to 40 bits.
Provides 14 VDC, 150 mA max. power for each card reader.
SOFTWARE SK-NET
TM
Software Version 2.0 or greater
OUTPUTS -
2 Per Door (Total of 4) Latch & Alarm Shunt DPDT contact, 2A, up to 220 VAC or 30 VDC
Auxiliary DPDT contact, 2A, up to 220 VAC or 30 VDC
INPUTS - 2 Per Door (Total of 4) Auxiliary 1 Requires SPST contact closure
Auxiliary 2 Requires SPST contact closure
COMMUNICATION RS-232 5-Wire Shielded Cable, up to 38.4K baud, full duplex, (8N1)
RS-485 Single Twisted Pair, shielded cable with a signal ground
Wiegand Input (2) Programmable up to 40 bits
14 VDC @ 150 mA supplied to each reader,
Modem Requires Hayes compatible - 1.2 to 38.4k baud
Printer Serial Printer (or Parallel printer with serial converter)
ENVIRONMENT Ambient Temperature -40° F to 158° F (-40° C to 70° C)
Humidity 0% to 95% relative humidity (non-condensing)
OPERATIONAL Card Capacity 65,535/Door (Highest card number = 65,535)
Time Zones 15 for card access, one door unlock; full week plus
holiday in one-half hour segments; 32 programmable
holidays; selectable automatic daylight saving time.
Facility Code Up to 16 different codes simultaneously (max. # of cards 65,535)
Latch/Alarm Shunt Timer Programmable from 1/4 to 30 seconds
Antipassback Real or Timed (1 to 30 minutes); hard or soft
Auxiliary Inputs (2) Programmable for door monitor, tamper monitor, remote
open, remote inactive, bell, arming circuit or user defined
Auxiliary Output (1) Output is programmable to activate under one of many
possible alarm conditions, time zone or card violations.
Limited Use Cards 4,000 (in a block within 65,535) programmable from
1-500 uses, days, weeks or number of days after first use.
Transaction Storage 4,864 events
Memory Non-volatile
This product complies with UL 294 Standards, CE (European Standards), and with Part 15 of Class B FCC Rules.
Per Door
{
SPECIFICATIONS
SK-ACP-LE