Softstart UK Busbar Adjustment Procedure
13. Busbar Adjustment Procedure
The busbars on non-bypassed models LV-DS-0360C ~ LV-DS-1600C can be adjusted for top or bottom input
and output as required.
NOTE
Many electronic components are sensitive to static electricity. Voltages so low that they cannot be
felt, seen or heard, can reduce the life, affect performance, or completely destroy sensitive electronic
components. When performing service, proper ESD equipment should be used to prevent possible
damage from occurring.
All units are manufactured with input and output busbars at the bottom of the unit as standard. The input
and/or output busbars can be moved to the top of the unit if required.
09275.B
1. Remove all wiring and links from the soft starter
before dismantling the unit.
2. Remove the unit cover (4 screws).
3. Remove the keypad faceplate, then gently
remove the keypad (2 screws).
4. Remove the control terminal plugs.
5. Gently fold the main plastic away from the starter
(12 screws).
6. Unplug the keypad loom from CON 1 (see note).
7. Label each SCR firing loom with the number of
the corresponding terminal on the backplane
PCB, then unplug the looms.
8. Unplug the thermistor, fan and current
transformer wires from the model board.
9. Remove the plastic tray from the starter (four
screws).
NOTE
Remove the main plastic slowly to avoid damaging the keypad wiring loom which runs between the
main plastic and the backplane PCB.
08605.A
10. Unscrew and remove the magnetic bypass plates
(models LV-DS-0620C to LV-DS-1600C only).
11. Remove the current transformer assembly (three
screws).
12. Identify which busbars are to be moved.
Remove the bolts holding these busbars in place
then slide the busbars out through the bottom of
the starter (four bolts per busbar).
08606.
A
13. Slide the busbars in through the top of the starter.
For input busbars, the short curved end should be
outside the starter. For output busbars, the
unthreaded hole should be outside the starter.
14. Replace the dome washers with the flat face
towards the busbar, then tighten the bolts holding
the busbars in place to 20 Nm.
15. Place the current transformer assembly over the
input busbars and screw the assembly to the
body of the starter (see note).
16. Run all wiring to the side of the starter and secure
with cable ties.