Specifications

Softstart UK Application Examples
10.4. Auxiliary Trip Circuit
In normal operation the LV-DS is controlled via a remote two-wire signal (terminals 56, 57).
Input A (terminals 53, 55) is connected to an external trip circuit (such as a low pressure alarm switch for a
pumping system). When the external circuit activates, the soft starter trips, which stops the motor.
K
M
1 F
1
22
21
6/T3
2
/
T
1
13
14
4/T
2
2
4
3
3
3
4
5/L3
3/L2
S3
S1
S
2
E
1/L1
6
5
64
4
1
40
5
6
57
5
8
53
5
5
A6
A5
A4
5
4
A
08
880
.A
6
3
1 2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
S1
Start/stop contact
S2
Reset contact
S3
Auxiliary trip contact
13, 14
Relay output A
21, 22, 24
Relay output B
33, 34
Relay output C
Parameter settings:
Parameter 6D Input A Function
Select 'Input Trip (N/O)'. Assigns the Input A to Auxiliary Trip (N/O) function.
Parameter 6E Input A Name
Select a name, eg Low Pressure. Assigns a name to Input A.
Parameter 4E Input A Trip
Set as required. For example, 'Run Only' limits the input trip to when the soft starter is running only.
Parameter 5E Input A Trip Delay
Set as required. Sets a delay between the input activating and the soft starter tripping.
Parameter 5F Input A Initial Delay
Set at around 120 seconds. Limits operation of the input trip to 120 seconds after the start signal.
This allows time for pressure to build up in the piping before the low pressure input becomes active.
710-15797-00A – LV-DS User Manual 53/64