Specifications
Application Examples Softstart UK
10.3. Emergency Run Operation
In normal operation the LV-DS is controlled via a remote two-wire signal (terminals 56, 57).
Emergency Run is controlled by a two-wire circuit connected to Input A (terminals 53, 55). Closing Input A
causes the LV-DS to run the motor and ignore certain trip conditions.
K
M
1 F
1
22
21
6/T3
2
/
T
1
13
14
4/T
2
2
4
3
3
3
4
5/L3
3/L2
S3
S1
S
2
E
1/L1
6
5
64
4
1
40
5
6
57
5
8
5
3
5
5
A6
A5
A4
5
4
A
0
887
9.A
6
3
1 2
4
5
+
+
1
Three-phase supply
2
Motor terminals
3
Control voltage
4
Remote control inputs
5
Motor thermistor input
6
Relay outputs
S1
Start/stop contact
S2
Reset contact
S3
Emergency Run Contact
13, 14
Relay output A
21, 22, 24
Relay output B
33, 34
Relay output C
Parameter settings:
• Parameter 6D Input A Function
• Select 'Emergency Run' - assigns Input A for Emergency Run function.
• Parameter 15C Emergency Run
• Select 'Enable' - Enables Emergency Run mode.
NOTE
Although the Emergency Run satisfies the functionality requirements of Fire Mode, Softstart UK
does not recommend its use in situations that require testing and/or compliance with specific
standards as it is not certified.