Specifications

Softstart UK Programming Menu
16 Protection Action
CAUTION
Defeating the protection may compromise the starter and motor, and should only be done in the case
of emergency.
16A~16M Protection Action
Options: Trip Starter (default)
Warn and Log
Log Only
Description: Selects the soft starter's response to each protection.
16A Motor Overload
16B Current Imbalance
16C Undercurrent
16D Instantaneous Overcurrent
16E Input A Trip
16F Frequency
16G Motor Thermistor
16H Excess Start Time
16I Starter Communication
16J Heatsink Overtemperature
16K Battery/Clock
16L Network Communication
16M Low Control Volts
8.5. Adjustment Lock
You can lock the Programming Menu to prevent users from altering parameter settings. The adjustment lock
can be turned on and off using parameter 15B.
To lock the programming menu:
1. Open the Programming Menu.
2. Open the Extended Menu.
3. Select 'Restricted'.
4. Enter the Access Code.
5. Select parameter 15B Adjustment Lock
6. Select and store 'Read Only'.
If a user attempts to change a parameter value when the adjustment lock is active, an error message is
displayed:
Access Denied
Adj Lock is On
8.6. Access Code
Critical parameters (parameter group 15 and higher) are protected by a four-digit security access code,
preventing unauthorised users from viewing or modifying parameter settings.
When a user attempts to enter a restricted parameter group, the keypad prompts for an access code. The
access code is requested once for the programming session, and authorisation continues until the user closes
the menu.
To enter the access code, use the EXIT and ENTER buttons to select a digit, and the
and buttons to
change the value. When all four digits match your access code, press ENTER. The keypad will display an
acknowledgement message before continuing.
Enter Access Code
0###
ENTER
Access Allowed
SUPERVISOR
To change the access code, use parameter 15A.
The default access code is 0000.
710-15797-00A – LV-DS User Manual 47/64