Specifications

Programming Menu Softstart UK
NOTE
If the starter is manually reset, the resets counter will return to zero.
9C Reset Delay Groups A&B
Range: 00:05 - 15:00 (minutes:seconds) Default: 5 seconds
Description: Sets the delay before resetting Group A and Group B trips.
9D Reset Delay Group C
Range: 5 - 60 (minutes) Default: 5 minutes
Description: Sets the delay before resetting Group C trips.
10 Display
10A Language
Options: English (default) Português
Chinese Français
Español Italiano
Deutsch Russian
Description: Selects which language the keypad will use to display messages and feedback.
10B, 10C, 10D, 10E User-Programmable Screen
Options:
Blank
Displays no data in the selected area, allowing long messages
to be shown without overlapping.
Starter State
The starter's operating state (starting, running, stopping or
tripped). Only available for top left and bottom left positions on
the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured on three phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal model.
kWh
The number of kilowatt hours the motor has run via the soft
starter.
Hours Run
The number of hours the motor has run via the soft starter.
Description: Selects which information will be displayed on the programmable monitoring screen.
10B User Screen - Top Left Default: Starter State
10C User Screen - Top Right Default: Blank
10D User Screen - Bottom Left Default: Hours Run
10E User Screen - Bottom Right Default: Blank
10F Graph Timebase
Options: 10 seconds (default)
30 seconds
1 minute
5 minutes
10 minutes
30 minutes
1 hour
Description: Sets the graph time scale. The graph will progressively replace the old data with
new data.
10G Graph Maximum
Range: 0% 600% Default: 400%
Description: Adjusts the upper limit of the performance graph.
10H Graph Minimum
Range: 0% 600% Default: 0%
Description: Adjusts the lower limit of the performance graph.
44/64 710-15797-00A – LV-DS User Manual