Specifications

Softstart UK Programming Menu
6D Input A Function
Options:
Motor Set Select
(default)
The LV-DS can be configured with two separate sets of
motor data.
To use the secondary motor data, parameter 6D must be set
to 'Motor Set Select' and 53, 55 must be closed when a start
command is given. The LV-DS checks which motor data to
use at a start, and will use that motor data for the entire
start/stop cycle.
Input Trip (N/O)
Input A can be used to trip the soft starter. When
parameter 6D is set to Input Trip (N/O), a closed circuit
across 53, 55 trips the soft starter.
Input Trip (N/C)
When parameter 6D is set to Input Trip (N/C), an open
circuit across 53, 55 trips the soft starter.
Local/Remote Select
Input A can be used to select between local and remote
control, instead of using the LOCAL/REMOTE button on the
keypad. When the input is open, the starter is in local mode
and can be controlled via the keypad. When the input is
closed, the starter is in remote mode. The START and
LOCAL/REMOTE buttons are disabled, and the soft starter
will ignore any Local/Remote select command from the
serial communications network.
To use Input A to select between local and remote control,
parameter 6A must be set to 'LCL/RMT Anytime' or
'LCL/RMT When Off'.
Emergency Run
In emergency run the soft starter continues to run until
stopped, ignoring all trips and warnings (see parameter 15C
for details).
Closing the circuit across 53, 55 activates emergency run.
Opening the circuit ends emergency run and the LV-DS
stops the motor.
Starter Disable
The LV-DS can be disabled via the control inputs. An open
circuit across 53, 55 will disable the starter. The LV-DS will
not respond to start commands. If running, the soft starter
will allow the motor to coast to stop, ignoring the soft stop
mode set in parameter 2H.
Jog Forward
Activates jog operation in a forward direction (will operate
only in Remote mode).
Jog Reverse
Activates jog operation in reverse direction (will operate only
in Remote mode).
Description: Selects the function of Input A.
6E Input A Name
Options: Input Trip (default) No Flow
Low Pressure Starter Disable
High Pressure Controller
Pump Fault PLC
Low Level Vibration Alarm
High Level
Description: Selects a message for the keypad to display when Input A is active.
710-15797-00A – LV-DS User Manual 41/64