Specifications
Programming Menu Softstart UK
• 3 Secondary Start/Stop
See the Primary Start/Stop parameters for parameter details.
3A – Start Mode-2
Options: Constant Current (default)
Adaptive Control
Description: Selects the soft start mode.
3B – Current Limit-2
Range: 100% - 600% FLC Default: 350%
Description: Sets the current limit for constant current and current ramp soft starting, as a
percentage of motor full load current.
3C – Initial Current-2
Range: 100% - 600% Default: 350%
Description: Sets the initial start current level for current ramp starting, as a percentage of motor
full load current. Set so that the motor begins to accelerate immediately after a start
is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
3D – Start Ramp Time-2
Range: 1 - 180 (seconds) Default: 10 seconds
Description: Sets the total start time for an Adaptive Control start or the ramp time for current ramp
starting (from the initial current to the current limit).
3E – Kickstart Level-2
Range: 100% - 700% FLC Default: 500%
Description: Sets the level of the kickstart current.
3F – Kickstart Time-2
Range: 0 - 2000 (milliseconds) Default: 0000 milliseconds
Description: Sets the kickstart duration. A setting of 0 disables kickstart.
3G – Excess Start Time-2
Range: 0:00 - 4:00 (minutes:seconds) Default: 20 seconds
Description: Set as required.
3H – Stop Mode-2
Options: Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Description: Selects the stop mode.
3I – Stop Time-2
Range: 0:00 - 4:00 (minutes:seconds) Default: 0 second
Description: Sets the stop time.
3J – Adaptive Start Profile-2
Options: Early Acceleration
Constant Acceleration (default)
Late Acceleration
Description: Selects which profile the LV-DS will use for an Adaptive Control soft start.
3K – Adaptive Stop Profile-2
Options: Early Deceleration
Constant Deceleration (default)
Late Deceleration
Description: Selects which profile the LV-DS will use for an Adaptive Control soft stop.
3L – Adaptive Control Gain-2
Range: 1% - 200% Default: 75%
Description: Adjusts the performance of Adaptive Control. This setting affects both starting and
stopping control.
38/64 710-15797-00A – LV-DS User Manual