Specifications
Softstart UK Programming Menu
Default Setting
7
Relay Outputs
7A Relay A Function
Main Contactor
7B Relay A On Delay
00:00 mm:ss
7C Relay A Off Delay
00:00 mm:ss
7D Relay B Function
Run
7E Relay B On Delay
00:00 mm:ss
7F Relay B Off Delay
00:00 mm:ss
7G Relay C Function
Trip
7H Relay C On Delay
00:00 mm:ss
7I Relay C Off Delay
00:00 mm:ss
7J Low Current Flag
50% FLC
7K High Current Flag
100% FLC
7L Motor Temperature Flag
80%
8
Analog Output
8A Analog Output A
Current (% FLC)
8B Analog A Scale
4-20 mA
8C Analog A Maximum Adjustment
100%
8D Analog A Minimum Adjustment
0%
9
Auto-Reset
9A Auto-Reset Action
Do Not Auto-Reset
9B Maximum Resets
1
9C Reset Delay Groups A&B
00:05 mm:ss
9D Reset Delay Group C
5 minutes
10
Display
10A Language
English
10B User Screen - Top Left
Starter State
10C User Screen - Top Right
Blank
10D User Screen - Bottom Left
Hours Run
10E User Screen - Bottom Right
Blank
10F Graph Timebase
10 seconds
10G Graph Maximum Adjustment
400%
10H Graph Minimum Adjustment
0%
10I Mains Reference Voltage
400 V
10J Display A or kW
Current
15
Restricted
15A Access Code
0000
15B Adjustment Lock
Read & Write
15C Emergency Run
Disable
15D Current Calibration
100%
15E Shorted SCR Action
3-Phase Control Only
15F Jog Torque
50%
15G Brake Torque
20%
15H Brake Time
00:01 mm:ss
15I Brake Torque-2
20%
15J Brake Time-2
00:01 mm:ss
16
Protection Action
16A Motor Overload
Trip Starter
16B Current Imbalance
Trip Starter
16C Undercurrent
Trip Starter
16D Instantaneous Overcurrent
Trip Starter
16E Input A Trip
Trip Starter
16F Frequency
Trip Starter
16G Motor Thermistor
Trip Starter
16H Excess Start Time
Trip Starter
16I Starter Communication
Trip Starter
16J Heatsink Overtemperature
Trip Starter
16K Battery/Clock
Trip Starter
16L Network Communication
Trip Starter
16M Low Control Volts
Trip Starter
710-15797-00A – LV-DS User Manual 35/64