Specifications
Programming Menu Softstart UK
8.3. Extended Menu
The Extended Menu provides access to all the LV-DS's programmable parameters.
Default Setting
1
Motor Details
1A Motor Full Load Current
Model dependent
1B Locked Rotor Time
00:10 mm:ss
1C Motor FLC-2
Model dependent
1D Locked Rotor Time-2
00:10 mm:ss
1E Dual Thermal Model
Single
2
Primary Start/Stop
2A Start Mode
Constant Current
2B Current Limit
350% FLC
2C Initial Current
350% FLC
2D Start Ramp Time
00:10 mm:ss
2E Kickstart Level
500% FLC
2F Kickstart Time
0 ms
2G Excess Start Time
00:20 mm:ss
2H Stop Mode
Coast To Stop
2I Stop Time
00:00 mm:ss
2J Adaptive Start Profile
Constant Acceleration
2K Adaptive Stop Profile
Constant Deceleration
2L Adaptive Control Gain
75%
3
Secondary Start/Stop
3A Start Mode-2
Constant Current
3B Current Limit-2
350% FLC
3C Initial Current-2
350% FLC
3D Start Ramp-2
00:10 mm:ss
3E Kickstart Level-2
500% FLC
3F Kickstart Time-2
0 ms
3G Excess Start Time-2
00:20 mm:ss
3H Stop Mode-2
Coast To Stop
3I Stop Time-2
00:00 mm:ss
3J Adaptive Start Profile-2
Constant Acceleration
3K Adaptive Stop Profile-2
Constant Deceleration
3L Adaptive Control Gain-2
75%
4
Protection Levels
4A Current Imbalance
30%
4B Phase Sequence
Any Sequence
4C Undercurrent
20% FLC
4D Instantaneous Overcurrent
400% FLC
4E Input A Trip
Always Active
4F Motor Temperature Check
Do Not Check
4G Frequency Check
Start/Run
4H Frequency Variation
±5 Hz
5
Protection Delays
5A Restart Delay
00:10 mm:ss
5B Current Imbalance Delay
00:03 mm:ss
5C Undercurrent Delay
00:05 mm:ss
5D Instantaneous Overcurrent Delay
00:00 mm:ss
5E Input A Trip Delay
00:00 mm:ss
5F Input A Initial Delay
00:00 mm:ss
5G Frequency Delay
00:01 mm:ss
6
Inputs
6A Local/Remote
LCL/RMT Anytime
6B Comms in Remote
Enable Control in RMT
6C Remote Reset Logic
Normally Closed (N/C)
6D Input A Function
Motor Set Select
6E Input A Name
Input Trip