Specifications
Softstart UK Programming Menu
8.2. Standard Menu
The standard menu provides access to commonly used parameters, allowing the user to configure the LV-DS
as required for the application.
Default Setting
1
Motor Details
1A Motor Full Load Current
Model dependent
2
Primary Start/Stop
2A Start Mode
Constant Current
2B Current Limit
350%
2C Initial Current
350%
2D Start Ramp Time
00:10 mm:ss
2G Excess Start Time
00:20 mm:ss
2H Stop Mode
Coast To Stop
2I Stop Time
00:00 mm:ss
4
Protection Levels
4B Phase Sequence
Any Sequence
4C Undercurrent
20% FLC
4D Instantaneous Overcurrent
400% FLC
4E Input A Trip
Always Active
5
Protection Delays
5C Undercurrent Delay
00:05 mm:ss
5D Instantaneous Overcurrent Delay
00:00 mm:ss
5E Input A Trip Delay
00:00 mm:ss
5F Input A Initial Delay
00:00 mm:ss
6
Inputs
6D Input A Function
Motor Set Select
6E Input A Name
Input Trip
7
Relay Outputs
7A Relay A Function
Main Contactor
7B Relay A On Delay
00:00 mm:ss
7C Relay A Off Delay
00:00 mm:ss
7D Relay B Function
Run
7E Relay B On Delay
00:00 mm:ss
7F Relay B Off Delay
00:00 mm:ss
7G Relay C Function
Trip
7H Relay C On Delay
00:00 mm:ss
7I Relay C Off Delay
00:00 mm:ss
7J Low Current Flag
50% FLC
7K High Current Flag
100% FLC
7L Motor Temperature Flag
80% FLC
10
Display
10A Language
English
10B User Screen - Top Left
Starter State
10C User Screen - Top Right
Blank
10D User Screen - Bottom Left
Hours Run
10E User Screen - Bottom Right
Blank
10J Display A or kW
Current