Specifications
Programming Menu Softstart UK
8.1. Quick Setup
The Quick Setup Menu makes it easy to configure the LV-DS for common applications. The LV-DS selects the
parameters relevant to the application and suggests a typical setting, and you can adjust each parameter to suit
your exact requirements.
Always set parameter 1A Motor Full Load Current to match the motor's nameplate full load current. The
suggested value is the starter's minimum full load current.
On the display, the highlighted values are suggested values and the values enclosed in a box are the loaded
values.
Application
Parameter
Suggested value
Pump Centrifugal
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Model dependent
Adaptive Control
Early Acceleration
10 seconds
Adaptive Control
Late Deceleration
15 seconds
Pump Submersible
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Stop Mode
Adaptive Stop Profile
Stop Time
Model dependent
Adaptive Control
Early Acceleration
5 seconds
Adaptive Control
Late Deceleration
5 seconds
Fan Damped
Motor Full Load Current
Start Mode
Current Limit
Model dependent
Constant Current
350%
Fan Undamped
Motor Full Load Current
Start Mode
Adaptive Start Profile
Start Ramp Time
Excess Start Time
Locked Rotor Time
Model dependent
Adaptive Control
Constant Acceleration
20 seconds
30 seconds
20 seconds
Compressor Screw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Model dependent
Constant Current
5 seconds
400%
Compressor Recip
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Model dependent
Constant Current
5 seconds
450%
Conveyor
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Model dependent
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
10 seconds
Crusher Rotary
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Model dependent
Constant Current
10 seconds
400%
30 seconds
20 seconds
Crusher Jaw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Model dependent
Constant Current
10 seconds
450%
40 seconds
30 seconds
32/64 710-15797-00A – LV-DS User Manual