Specifications

Operation Softstart UK
Programmable screen
The LV-DS's user-programmable screen can be configured to show the most important information for the
particular application. Use parameters 10B to 10E to select which information to display.
Ready
0000 hrs
Motor Temperature
The temperature screen shows which motor data set is in use, and the temperature of both motors as a
percentage of total thermal capacity. If the LV-DS is configured for use on one motor, the temperature for the
secondary motor (M2) will always show 0%.
Primary Motor Set
M1 000% M2 000%
Current
The current screen shows real-time line current on each phase.
Phase Currents
000.0A 000.0A 000.0A
Motor Power
The motor power screen shows motor power (kW, HP and kVA) and power factor.
000.0kW 0000HP
0000kVA -. - - pf
Last Start Information
The last start information screen shows details of the most recent successful start:
start duration (seconds)
maximum start current drawn (as a percentage of motor full load current)
calculated rise in motor temperature
Last start010 s
350 % FLC
Temp 5%
Date and Time
The date/time screen shows the current system date and time (24 hour format). For details on setting the
date and time, see Set Date and Time on page 48.
SCR Conduction Bargraph
The SCR conduction bargraph shows the level of conduction on each phase.
L1 Cond
L2 Cond
L3 Cond
Graphs
The LV-DS can display real-time performance information for:
current
motor temperature
motor kW
motor kVA
motor power factor
The newest information is displayed at the right hand edge of the screen. Older data is not stored.
To access the graphs or to change which graph is shown, press the GRAPHS button.
The graph can also be paused, to allow past performance to be analysed. To pause the graph, press and hold
the GRAPHS button for more than 0.5 seconds. To unpause the graph, press the GRAPHS button again.
NOTE
The LV-DS will not collect data while the graph is paused. When graphing resumes, a small gap
will be shown between the old data and the new data.
7.4. Start, Stop and Reset Commands
The soft starter can be controlled in three ways:
using the buttons on the keypad
via remote inputs
via a serial communication link
The LOCAL/REMOTE button controls whether the LV-DS will respond to local control (via the keypad) or
remote control (via the remote inputs). The LV-DS can also be set to allow local control only or remote control
only, using parameter 6A Local/Remote. The Local LED on the keypad is on when the soft starter is in local
control mode and off when the soft starter is in remote control mode.
24/64 710-15797-00A – LV-DS User Manual