Specifications

Softstart UK Power Circuits
NOTE
Fuse selection is based on a 400% FLC start for 20 seconds in conjunction with standard
published starts per hour, duty cycle, 40°C ambient temperature and up to 1000 m altitude. For
installations operating outside these conditions, consult your local supplier.
These fuse tables contain recommendations only. Always consult your local supplier to confirm
the selection for your particular application.
Bussman Fuses - Square Body (170M)
Model
SCR I
2
t (A
2
s)
Supply Voltage
(
<
440 VAC)
Supply Voltage
(
<
575 VAC)
Supply Voltage
(
<
690 VAC)
LV-DS-0023B
1150
170M1314
170M1314
170M1314
LV-DS-0043B
8000
170M1316
170M1316
170M1316
LV-DS-0050B
10500
170M1318
170M1318
170M1318
LV-DS-0053B
15000
170M1318
170M1318
170M1318
LV-DS-0076B
15000
170M1319
170M1319
170M1318
LV-DS-0097B
51200
170M1321
170M1321
170M1319
LV-DS-0100B
80000
170M1321
170M1321
170M1321
LV-DS-0105B
125000
170M1321
170M1321
170M1321
LV-DS-0145B
125000
170M1321
170M1321
170M1321
LV-DS-0170B
320000
170M2621
170M2621
170M2621
LV-DS-0200B
320000
170M2621
170M2621
170M2621
LV-DS-0220B
320000
170M2621
170M2621
170M2621
LV-DS-0255B
320000
170M2621
170M2621
170M2621
LV-DS-0255C
320000
170M2621
170M2621
170M2621
LV-DS-0350B
202000
170M5011
170M5011
––
LV-DS-0360C
320000
170M6010
170M6010
170M6010
LV-DS-0380C
320000
170M6011
170M6011
––
LV-DS-0425B
320000
170M6011
––
––
LV-DS-0430C
320000
170M6011
170M6011
––
LV-DS-0500B
320000
170M6008*
––
––
LV-DS-0580B
781000
170M6013
170M6013
170M6013
LV-DS-0620C
1200000
170M6015
170M6015
170M6014
LV-DS-0650C
1200000
170M6015
170M6015
170M6014
LV-DS-0700B
781000
170M5015
170M5015
––
LV-DS-0790C
2530000
170M6017
170M6017
170M6016
LV-DS-0820B
1200000
170M5017
170M6015
––
LV-DS-0920B
2530000
170M6017
170M6017
––
LV-DS-0930C
4500000
170M6019
170M6019
170M6019
LV-DS-1000B
2530000
170M6018
170M6013*
––
LV-DS-1200C
4500000
170M6021
––
––
LV-DS-1410C
6480000
––
––
––
LV-DS-1600C
12500000
170M6019*
––
––
* Two parallel connected fuses required per phase.
Bussman Fuses - British Style (BS88)
Model
SCR I
2
T (A
2
S)
Supply Voltage
(
<
440 VAC)
Supply Voltage
(
<
575 VAC)
Supply Voltage
(
<
690 VAC)
LV-DS-0023B
1150
63FE
63FE
63FE
LV-DS-0043B
8000
120FEE
120FEE
120FEE
LV-DS-0050B
10500
120FEE
120FEE
120FEE
LV-DS-0053B
15000
200FEE
200FEE
200FEE
LV-DS-0076B
15000
200FEE
200FEE
200FEE
LV-DS-0097B
51200
200FEE
200FEE
200FEE
LV-DS-0100B
80000
280FM
280FM
280FM
LV-DS-0105B
125000
280FM
280FM
280FM
LV-DS-0145B
125000
280FM
280FM
280FM
LV-DS-0170B
320000
450FMM
450FMM
450FMM
LV-DS-0200B
320000
450FMM
450FMM
450FMM
LV-DS-0220B
320000
450FMM
450FMM
450FMM
LV-DS-0255B
320000
450FMM
450FMM
450FMM
LV-DS-0255C
320000
450FMM
450FMM
450FMM
710-15797-00A – LV-DS User Manual 19/64