Specifications
Softstart UK Power Circuits
• In-line installation, non-bypassed
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1 F1
M
3
KM1
Main contactor (optional)
F1
Semiconductor fuses
(optional)
• Inside delta installation, internally bypassed
0
4479
.C
M
3
6/
T
3
2
/
T
1
13
14
4/T2
KM
1
U1(1) U2(4)
V
1
(2
)
V2
(
5)
W
1
(
3
)
W
2
(
6
)
5/L
3
3
/
L
2
1
/
L
1
E
KM
1
F1
KM1
Main contactor
F1
Semiconductor fuses
(optional)
CAUTION
When connecting the LV-DS in inside delta configuration, always install a main contactor or shunt trip
circuit breaker.
• Inside delta installation, externally bypassed
Non-bypassed models have dedicated bypass terminals, which allow the LV-DS to continue providing protection
and monitoring functions even when bypassed via an external bypass contactor.
The bypass contactor must be connected to the bypass terminals and controlled by a programmable output
configured to Run (see parameters 7A~7I).
M
3
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
KM1
KM1 F1
U1(1) U2(4)
V1(2)
V2(5)
W1(3) W2(6)
L2B
*
L1B
*
L3B
*
KM2
34
33
KM2
KM1
Main contactor
KM2
Bypass contactor (external)
F1
Semiconductor fuses
(optional)
NOTE
The bypass terminals on LV-DS-0255C are T1B, T2B, T3B. The bypass terminals on
LV-DS-0360C ~ LV-DS-1600C are L1B, L2B, L3B.
The fuses can be installed on the input side if required.
710-15797-00A – LV-DS User Manual 17/64