Specifications

Softstart UK Installation
5.6. Power Terminations
NOTE
For personnel safety, the power terminals on models up to LV-DS-0105B are protected by snap-off
tabs. When using large cables, it may be necessary to break off these tabs.
NOTE
Some units use aluminium busbars. When connecting power terminations, we recommend
cleaning the surface contact area thoroughly (using an emery or stainless steel brush) and using
an appropriate jointing compound to prevent corrosion.
Use only copper stranded or solid conductors, rated for 75 ºC or higher.
LV-DS-0023B~LV-DS-0105B
05966.E
Cable size:
6-50 mm
2
(AWG 10-1/0)
Torque: 4 Nm (2.9 ft-lb)
11290.A
14 mm (0.55 inch)
Torx T20 x 150
Flat 7 mm x 150
LV-DS-0145B
LV-DS-0170B~LV-DS-0220B
LV-DS-0255B
19 Nm (14.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
6 mm
19 mm
8.5 mm
(M8)
08351.
B
08352.B
6 m
m
19
m
m
10.5 mm
(M10)
5 mm
28 mm
11 mm
(M10)
131
81.
B
LV-DS-0350B~LV-DS-0425B
LV-DS-0500B~LV-DS-1000B
LV-DS-0255C
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
38 Nm (28.0 ft-lb)
6 mm
28 mm
11 mm
(M10)
14
543.A
13 mm
32 mm
11 mm
(M10)
098 6 6.B
6
mm
3
2 m
m
1
0
.5
mm
(
M1
0
)
08353.B
LV-DS-0360C~LV-DS-0930C
LV-DS-1200C~LV-DS-1600C
38 Nm (28.0 ft-lb)
66 Nm (48.7 ft-lb)
1
3 mm
32 m
m
10
.5
m
m
(
M1
0
)
08354.B
16
mm
5
1 mm
12.5
mm
(
M12
)
08355.B
710-15797-00A – LV-DS User Manual 13/64