High-Speed Input and Pulse Output Features
DL105 PLC User Manual, 3 rd Edition
Recall that V7633 is the HSIO Mode Select register. Refer to the diagram below. Use
BCD 50 in the lower byte to select High-Speed Counter Mode. Use BCD 00 or 20 in
the upper byte as required. Combine the two bytes into a data word “xx50”, for writing
to V7633.
015 14 13 12
Memory Location V7633
11 10 123456789Bits
00100010100
HSIO Mode Setup (BCD)Miscellaneous Setup (BCD)
0000
00 = Power Up in Previous Mode
20 = Power Up in Run Mode Always 50 = Pulse Catch Input
20 05
0
Choose the most convenient method of programming V7633 from the following:
S Include load and out instructions in your ladder program
S DirectSOFT’s memory editor
S Use the Handheld Programmer D2--HPP
We recommend using the first method above so that the HSIO setup becomes an
integral part of your application program. An example program later in this section
shows how to to this.
The configurable discrete input options for Pulse Catch Mode are listed in the table
below. Input X0 is the pulse input, and must have “0005” loaded into it configuration
register V7634. Inputs X1, X2, and X3 can only be filtered inputs. Each input has its
own configuration register and filter time constant.
Input Configuration
Register
Function Hex Code
Required
X0 V7634 Pulse Catch Input 0005
X1 V7635 Filtered Input xx06 (xx = filter time)
X2 V7636 Filtered Input xx06 (xx = filter time)
X3 V7637 Filtered Input xx06 (xx = filter time)
Setup for Mode 50
X Input
Configuration