Specifications

X Input Configuration
The configurable discrete input options for Pulse Catch Mode are listed in the table below.
Each input has its own configuration register and filter time constant.
DL06 Micro PLC User Manual, 3rd Edition, Rev. C
E–74
Appendix E: High-speed Input and Pulse Output Features
1
2
3
4
E
6
7
8
9
10
11
12
13
14
A
B
C
D
Input Configuration Register Function Hex Code Required
X0 V7634 Pulse Catch Input 0005 (default)
X1 V7635
Interrupt 0004
Pulse Catch Input 0005 (default)
Filtered Input xx06 (xx = filter time) 0 - 99 ms (BCD)
X2 V7636
Interrupt 0004
Pulse Catch Input 0005 (default)
Filtered Input xx06 (xx = filter time) 0 - 99 ms (BCD)
X3 V7637
Interrupt 0004
Pulse Catch Input 0005 (default)
Filtered Input xx06 (xx = filter time) 0 - 99 ms (BCD)