Specifications
Default Mode
Mode 60 (Filtered Inputs) is the default mode. The DL06 is initialized to this mode at the
factory, and any time you initialize the scratchpad memory. In the default condition, X0–X3
are filtered inputs (10 ms delay) and Y0–Y1 are standard outputs.
DL06 Micro PLC User Manual, 3rd Edition, Rev. C
E–5
Appendix E: High-speed Input and Pulse Output Features
1
2
3
4
E
6
7
8
9
10
11
12
13
14
A
B
C
D
Physical I/O Point Usage
Mode
DC Input Points DC Output Points
X0 X1 X2 X3 Y0 Y1
10
High-Speed Counter Counter #1
Counter #2,
Interrupt,
Pulse Input or
Filtered Input
Reset #1,
Interrupt,
Pulse Input or
Filtered Input
Reset #2,
Interrupt,
Pulse Input or
Filtered Input
Regular
Output
Regular
Output
20
Up/Down counter
(Standard counting)
Up Counting
Down
Counting
Reset,
Pulse Input or
Filtered Input
Pulse Input or
Filtered Input
Regular
Output
Regular
Output
Up/Down counter
(Quadrature counting)
Phase A
Input
Phase B Input
30
Pulse Output
Pulse Input
or Filtered
Input
Pulse Input or
Filtered Input
Pulse Input or
Filtered Input
Pulse Input or
Filtered Input
Pulse or
CW Pulse
Direction or
CCW Pulse
40
High-Speed Interrupt Interrupt
Interrupt,
Pulse Input or
Filtered Input
Interrupt,
Pulse Input or
Filtered Input
Interrupt,
Pulse Input or
Filtered Input
Regular
Output
Regular
Output
50
Pulse Catch Pulse Input
Pulse Input,
Interrupt or
Filtered Input
Pulse Input,
Interrupt or
Filtered Input
Pulse Input,
Interrupt or
Filtered Input
Regular
Output
Regular
Output
60
Filtered Input Filtered Input Filtered Input Filtered Input Filtered Input
Regular
Output
Regular
Output