Specifications

Troubleshooting Guide for Mode 20
If youre having trouble with Mode 20 operation, please study the following symptoms and
possible causes. The most common problems are listed below.
Symptom: The counter does not count.
Possible causes:
1. Field sensor and wiring – Verify that the encoder or other field device inputs actually turn on and
illuminate the status LEDs for X0 and X1. A standard incremental encoder will visibly, alternately
turn on the LEDs for X0 and X1 when rotating slowly (1 RPM). Or, the problem could be due to
a sinking-sourcing wiring problem, etc. Remember to check the signal ground connection. Also
verify that the pulse on-time, duty cycle, voltage level, and frequency are within the input
specifications.
2. Configuration – make sure all of the configuration parameters are correct. V7633 must be set to
20, and V7634 must be set to “0002” to enable the Phase A input, and V7635 must be set to
“0000” to enable the Phase B input.
3. Stuck in reset – check the input status of the reset input, X2. If X2 is on, the counter will not
count because it is being held in reset.
4. Ladder program – make sure you are using counter CT174 in your program. The top input is the
enable signal for the counter. It must be on before the counter will count. The middle input is the
dummy input and must be off for the counter to count. The bottom input is the counter reset, and
must be off during counting.
Symptom: The counter counts in the wrong direction
(up instead of down, and visa-versa).
Possible causes:
1. Channel A and B assignment – It’s possible that Channel A and B assignments of the encoder
wires is backwards from the desired rotation/counting orientation. Just swap the X0 and X1 inputs,
and the counting direction will be reversed.
Symptom: The counter counts up and down but will not reset.
Possible causes:
1. Check the LED status indicator for X2 to make sure it is active when you want a reset. Also verify
the configuration register V7636 for X2 is set to 7. Or, if you are using an internal reset, use the
status mode of DirectSOFT to monitor the reset input to the counter.