Specifications
DL06 Micro PLC User Manual, 3rd Edition, Rev. C
E–28
Appendix E: High-speed Input and Pulse Output Features
1
2
3
4
E
6
7
8
9
10
11
12
13
14
A
B
C
D
X Input Configuration
The configurable discrete input options for High-Speed Counter Mode are listed in the table
below. The section on Mode 60 operation at the end of this appendix describes programming
the filter time constants.
Mode 20 Up/Down Counter
Input
Configuration
Register
Function Hex Code Required
X0 V7634
Up counting
0202 (standard, absolute)
0302 (standard, incremental)
Phase A
0002 (quadrature, absolute) (default)
0102 (quadrature, incremental)
1002 (quadrature, absolute) 4x counting*
1102 (quadrature, incremental) 4x counting*
X1 V7635 Down counting or Phase B 0000
X2 V7636
Counter Reset (no interrupt)
0007** (default)
0207**
Counter Reset (with interrupt)
0107**
0307**
Pulse input 0005
Filtered input xx06 (xx = filter time, 0 - 99ms (BCD)
X3 V7637
Pulse input 0005
Filtered input xx06 (xx = filter time, 0 - 99ms (BCD) (default)
* With this feature, you can count 4 times more with the same encoder.
** With the counter reset you have the option of a normal reset or a faster reset. However, the fast
reset does not recognize changed preset values during program execution. When ‘0007’ or ‘0107’
are set in V7636 and preset values are changed during program execution, the DL06 recognizes the
changed preset values at the time of the reset. When ‘0207’ or ‘0307’ are set in V7636 the CPU
does not check for changed preset values, so the DL06 has a faster reset time.
Phase A
Phase B
Normal counting
1 2 3 4
4x counting
1 2 3 4 5 6 7 8 10 119 12 13 14 15 16