Specifications

DL05 Micro PLC User Manual, 6th Edition, Rev. C
E–7
Appendix E: High-speed Input and Pulse Output Features
1
2
3
D
E
6
7
8
9
10
11
1
1
14
A
B
C
D
Wiring Diagram
A general wiring diagram for counters/encoders to the DL05 in HSIO Mode 10 is shown
below. Many types of pulse-generating devices may be used, such as proximity switches,
single-channel encoders, magnetic or optical sensors, etc. Devices with sinking outputs (NPN
open collector) are probably the best choice for interfacing. If the counter sources to the
inputs, it must output 12 to 24 VDC. Note that devices with 5V sourcing outputs will not
work with DL05 inputs.
Interfacing to Counter Inputs
Interfacing to Counter Outputs
The DL05’s DC inputs are flexible in that they detect current flow in either direction, so they
can be wired to a counter with either sourcing or sinking outputs. In the following circuit, a
counter has open-collector NPN transistor outputs. It sinks current from the PLC input
point, which sources current. The power supply can be the FA–24PS or another supply
(+12VDC or +24VDC), as long as the input specifications are met.
In the next circuit, an encoder has open-emitter PNP transistor outputs. It sources current to
the PLC input point, which sinks the current back to ground. Since the encoder sources
current, no additional power supply is required. However, note that the encoder output must
be 12 to 24 volts (5V encoder outputs will not work).
Counter Input Wiring
Signal Common
Signal
+
Counter Output
+
X0 Input
Output
Ground
Input
Common
12-24 VDC Supply
(sinking)
(sourcing)
X0 Input
Output (sourcing)
:
Ground
Common
+12 to 24 VDC
(sinking)
Counter Output
Input