Specifications
Filtered Inputs Program Example
The following program selects Mode 60, then programs the filter delay time constants for
inputs X0, X1, and X2. Each filter time constant is different, for illustration purposes. The
program is otherwise generic, and may be adapted to your application.
DL05 Micro PLC User Manual, 6th Edition, Rev. C
E–54
Appendix E: High-speed Input and Pulse Output Features
1
2
3
D
E
6
7
8
9
10
11
1
1
14
A
B
C
D
SP0
LD
K60
Load constant K60 into the accumulator. This
selects Mode 60 as the HSIO mode.
OUT
V7633
Output the constant to V7633, the location of the
HSIO Mode select register.
DirectSOFT
Mode 60
LD
K2006
Load the constant K2006 which is required to select
filtered inputs with a 20 ms filter time constant.
OUT
V7635
Output this constant to V7635, configuring X1.
Filtered Inputs
OUT
V7636
Output this constant to V7636, configuring X2.
LD
K1006
Load the constant K1006 which is required to configure
filtered inputs with a time constant of 10 ms.
OUT
V7634
Output this constant to V7634, configuring X0.
END
END coil marks the end of the main program..
Main Program
Insert Main Program rungs here for your application.
LD
K5006
Load the constant K5006 which is required to select
filtered inputs with a 50 ms filter time constant.