Specifications
Mode 50: Pulse Catch Input
Purpose
The HSIO circuit has a pulse-catch mode of operation. It monitors the signal on input X0,
preserving the occurrence of a narrow pulse. The purpose of the pulse catch mode is to enable
the ladder program to “see” an input pulse which is shorter in duration than the current scan
time. The HSIO circuit latches the input event on input X0 for one scan. This contact
automatically goes off after one scan.
Functional Block Diagram
Refer to the block diagram below. When the lower byte of HSIO Mode register V7633
contains a BCD “50”, the pulse catch mode in the HSIO circuit is enabled. X0 automatically
becomes the pulse catch input, which sets the latch on each rising edge. The HSIO resets the
latch at the end of the next CPU scan. Inputs X1 and X2 are available as filtered discrete inputs.
Pulse Catch Timing Parameters
Signal pulses at X0 must meet certain timing criteria to guarantee a pulse capture will result. Refer
to the timing diagram below. The input characteristics of X0 are fixed (it is not a programmable
filtered input). The minimum pulse width is 0.1 ms. There must be some delay before the next
pulse arrives, such that the pulse period cannot be smaller than 0.5 ms. If the pulse period is
smaller than 0.5 ms, the next pulse will be considered part of the current pulse.
NOTE The pulse catch and filtered input functions are opposite in nature. The pulse catch feature on
X0 seeks to capture narrow pulses, while the filter input feature on X1 and X2 seeks to reject narrow
pulses.
DL05 Micro PLC User Manual, 6th Edition, Rev. C
E–49
Appendix E: High-speed Input and Pulse Output Features
1
2
3
D
E
6
7
8
9
10
11
1
1
14
A
B
C
D
Time
Pulse
Input
X0
0.1 ms minimum
0.5 ms minimum
Input Circuit
CPU
PLC
DL05
X0
Y0, Y1
X3 - X7
Y2 -Y5
V-memory
V7633 0050
Mode select
I/O data
HSIO
LATCH
Set
Reset
X1, X2
scan
FILTER
Output Circuit