User manual
Chapter 2 Installation
16 ADVANCED MICRO CONTROLS INC.
Autotech Transducer Installation
Transducer Mounting
The 1761H module directly support Autotech SAC-RL210-G128 transducers. The Autotech
SAC-RL210-G64 transducers are not supported by AMCI. Refer to Autotech literature for
dimensional drawings and mounting recommendations.
Transducer Wiring
Table 3.5 is a wiring table for all supported Autotech transducers. The table cross references
resolver designations, AMCI wire color, Autotech terminal and connector pin-outs, and
Transducer Input Connector pin-out.
1) Autotech CBL-10T22 cable is not supported. Belden 9731 or exact
equivalent must be used.
2) Cable drawings for connecting Autotech transducers are available. If you
want a cable drawing instead of using the table, contact AMCI. A drawing
will be faxed to you upon request.
9731
Wire Color
Resolver
Designation
SAC-RL210
Terminals
SAC-RL210
MS Connector
1761H
Connector
RED R1 1 A 1
BLK/RED
1
R2 2 B 2
BRN R1 1 A 1
BLK/BRN
1
R2 2 B 2
WHT CS1 3 C 6
BLK/WHT
1
CS3 5 E 4
BLK/GRN
1
CS2 4 D 5
GRN CS4 6 F 4
YEL FS1 7 H 4
BLK/YEL
1
FS3 9 L 8
BLK/BLU
1
FS2 8 K 4
BLU FS4 10 M 7
1: Denotes black wire of black and colored wire pair.
Table 2.5 Autotech Transducer Wiring
Do not, under any circumstances, connect the shields of the
transducer cable to the earth ground connection of the transducer.
This connection could form a ground loop that may damage the
1761H module or PLC. The earth ground connection on the MS
style connectors is pin G. The earth ground connection on the
screw terminal transducers is the green screw.