User Guide
*** Main Menu***
Initialize
A-01: Access Level
z Use Constant A-01 to select the user constant access level.
This level determines which user constants can be changed and displayed.
Settings:
A-01=Constant Set (Factory Setting)
This setting allows all user constants to be changed and displayed.
A-01=Operation Only
This setting allows the “Operation” and “Initialize” to be changed or displayed.
A-02: Init Parameters
z Use Constant A-02 to initialize the user constants.
z When initialized, the user constants will return to their factory preset values. You
should normally record the setting of any constants that are changed from factory
presets.
Settings:
A-02=Preset Setting
This setting allows to initialize the user constants to factory settings.
A-02=No Initialize (Factory Setting)
This setting does not initialize any user constants.
A-03: Password 1
A-04: Password 2
z These two constants are reserved for the factory to test and set the functions.
z Users are not allowed to set these two constants.
Lock the constants setting
1. Finish setting all the programmable constants to the desired values.
2. Change A-01=Operation Only, factory setting is A-01=Constants Set.
3. Use UP key to go to A-03 to enter the password 1 (max. 4 digits)
5-4