User Guide

Main Menu Group Constant LCD Display Range Unit
Factory
Setting
Remark Page
B-05 BAT. MAX Charge Amps 0~80 1A
NOTE 6 5-6
FLOOD-
ED
13.9~15.2 0.1V 14.6 5-6
AGM 13.7~15.1 0.1V 14.1 5-6
B-06
Set Absorption
Volts
GEL 13.6~15.1 0.1V 14.1 5-6
B-07 Set Absorption Time
0~ 99 Hr
59 Min
1 Min 2 Hr 5-7
FLOOD-
ED
12.9~14.2 0.1V 13.8 5-7
AGM 12.8~14.2 0.1V 13.2 5-7
B-08
Set Float
Voltage
GEL 12.8~14.1 0.1V 13.5 5-7
B-09 Set Equalize Voltage
12V:14.7~16.4
24V:29.4~32.8
36V:44.1~49.2
48V:58.8~65.6
0.1V
12V:15.6
24V:31.2
36V:46.8
48V:62.4
NOTE 3 5-7
B-10 Set MAX EQU. Time
0~
99 Hr 59 Min
1 Min 2 Hr NOTE 3 5-7
B-11 Set Days Between EQU 0~999 1 Day OFF NOTE 3 5-7
B
B-12 Manual Equalize YES/NO
NO NOTE 3 5-8
MPPT Setup
P and O
Scan and Hold
Percentage
C-01 Set MPPT Type
Hold Input V
P and O 5-8
C-02 Set Scan Frequency 1~4Hr 1 Min 1 Hr NOTE 4 5-8
C-03 Set Percentage VOC 0~100 1% 80 NOTE 4 5-9
C-04 Percentage EveryTime 1~4Hr 1 Min 1 Hr NOTE 4 5-9
Programming
C
C-05 Set Hold Input Volts 0~140/0~240 0.1V
NOTE 4
NOTE 6
5-9
4-2