Specifications

1. The DACS shall be capable of activating 128 additional relay outputs for auxiliary
functions based on its classifications (area vs. panel wide). Output Expansion
Modules shall be able to be located rem ote to the m ain panel to a m aximum distance
of 1000 feet. 8 relays (Form C) are to be provided per octo-relay m odule
2. The DACS shall be capable of activating 64 additional relay outputs for auxiliary
functions based on its classifications (area vs. panel wide). Output Expansion
Modules shall be able to be located rem ote to the m ain panel to a m aximum distance
of 1000 feet. 8 relays (Form C) are to be provided per octo-relay m odule
3. The DACS shall be capable of activating 24 additional relay outputs for auxiliary
functions based on its classifications (area vs. panel wide). Output Expansion
Modules shall be able to be located rem ote to the m ain panel to a m aximum distance
of 1000 feet. 8 relays (Form C) are to be provided per octo-relay m odule
4. The DACS shall be capable of activating 16 additional relay outputs for auxiliary
functions based on its classifications (area vs. panel wide). 8 relays (Form C) are to
be provided per octo-relay module
5. The DACS shall be capable of activating 8 additional relay outputs for auxiliary
functions based on its classifications (area vs. panel wide). 8 relays (Form C) are to
be provided per octo-relay module
6. The DACS shall be capable of controlling relays and automatically executing system
functions based on a tim e / event scheduling program . The program can be hour, day
of week or day of m onth based.
7. Relays and other outputs m ay be program med to follow up to 14 different area
conditions or up to 12 panel conditions. Relays m ay also be program m ed to follow
individual points or groups of points.
8. The DACS shall support 4 different types of alarm output selections: Steady, Pulsed,
California Standard, and Temporal Code 3.
E. Scheduling: The DACS shall support scheduling capabilities with the following
characteristics:
1. Arm / Disarm specific area(s) based on open/close windows.
2. Bypass / Unbypass point(s).
3. Activate / Deactivate relay(s).
4. Send test reports.
5. Up to 4 program m able holiday schedules of 366 days each (includes leap year).
Based on the holiday settings, different tim e windows for open/close and other system
functions can be executed.
6. Autom atic adjustm ent of system clock for daylight savings time.
7. Turn an Access Authority Level On / Off.
8. Hold a Door Open (unlocked and shunted).
9. Secure a Door Closed (locked, no valid cards will allow entry).
10. Return a Door to Norm al Operation (locked, valid cards will allow entry).
11. Turn recording of Access Granted events On/ Off (and transm ittal if routing is ON).
12. Turn recording of Access Denied events On/ Off (and transm ittal if routing is ON).
F. Alarm Com m and Centers:
1. The DACS shall accom m odate connection with up to 32 ACCs, each capable of
displaying custom English text on touch screen liquid crystal or vacuum fluorescent
(VF) displays.
2. The Alarm Com m and Centers shall accomm odate viewing and configuration of
system param eters including:
a. Network Param eters:
1) DHCP Enable/Disable for the selected network m odule.
2) UPnP Enable/Disable for the selected network module.
3) IP Address for the selected network m odule
4) Subnet Mask for the selected network m odule.
5) Default Gateway for the selected network m odule.
6) Port Num ber for the selected network m odule - The module's port
num ber shall range from 0 to 65,535.
7) DNS Server Address for the selected m odule's DNS server IP address
8) DNS Host Nam e for the selected module. The DNS host nam e shall
Page 6