Specifications

not listed other than model num ber. The control panel shall support the following:
a. The DACS system is capable of being utilized as a com bination Intrusion and
Fire system per code. Fully integrated intrusion, access and fire functions allow
users to interface with 1 system instead of 3
b. Integrated Telephone Line Interface with programm able options for signaling
and supervision.
c. Conettix IP based com m unication option provides high-speed, secures alarm
transport and control.
d. 32 program m able areas with perim eter and interior partitioning.
e. 8 on-board, class B hardwired points with expansion capability for a total of 246
wired or wireless points.
f. Compatibility with touch-screen color LCD, vacuum fluorescent, ATM style LCD
or LED style Alarm Com m and Centers.
g. Local or rem ote program ming, test, and diagnostic capability via a computer
running the Rem ote Programm ing Software (RPS).
h. The system shall support the use of an Apple iOS device for control. Functions
to include arming, disarm ing, control of outputs, lock, unlock, cycle and secure
access doors.
i. Integrated real tim e clock, calendar, test tim er and program m able scheduling
capability for relay control and autom atic execution of system functions based
on a tim e / event.
j. Provide 1.4 am ps of power for standby operation and 2 am ps of alarm power,
both rated at 12 VDC.
k. 2 wet-contact relay outputs and 1 Auxiliary wet-contact relay output with
expansion capability for up to an additional 128 dry-contact relay outputs.
l. Integrated battery charger with reverse hook up protection, battery supervision
and battery deep discharge protection.
m. Supervision of peripheral devices and communications interface(s).
B. Point Functionality and Expansion:
1. Each point in the system shall be program mable to provide the following type of
response in the system:
a. Always on (24 hour response).
b. On when the system is Master Arm ed.
c. Only on when the system is Perim eter Arm ed.
d. Displays / Does Not Display at the ACC when the point is activated.
e. Provides / Does Not provide entry warning tone.
f. Sounds / Does Not Sound audible alarm indication.
g. The Point is by passable / not by passable.
h. Alarm Verification with program m able verification time.
i. Relay activation by Point.
j. Provides / Does Not Provide "watch point" capability.
k. Provides Swinger Bypass.
l. Defers Bypass Report.
m. Can return to the system after being force arm ed and then restoring.
n. Can return to the system after being bypassed and then restoring.
2. The DACS shall be capable of supporting "group zoning." Group zoning refers to the
com bining of points into a separately identifiable and separately annunciated
(program m able text) areas.
3. The DACS shall be capable of allowing variable point response tim es via
programm ing. Point response tim es shall be program mable over a range of 300
milliseconds to 4.5 seconds.
4. The DACS shall have the capability to expand up to 246 separately identifiable points,
of which 8 are on-board and 238 are off-board wired or wireless addressable points
connected to m ultiplexed backbone trunks via wired modules and/or wireless
receivers.
a. The 8 on-board points shall be able to accom m odate powered class B
functionality using a powered loop interface m odule.
b. Point Expansion Modules (W ired and W ireless) shall be able to be located
rem ote to the main panel to a m axim um distance of 1000 feet.