1.1 Health and Safety
AmbiRad heaters must be installed in
accordance with the relevant provisions of the
Gas Safety (Installations and Use) Regulations
1998. Due account should also be taken of any
obligations arising from the Health and Safety
at Works Act 1974 or relevant codes of
practice. In addition the installation must be
carried out in accordance with the current IEE
wiring regulations (BS 7671), BS 6896
(Industrial & Commercial) and any other
relevant British Standards and Codes of
Practice by a qualified installer. Isolate all
electrical supplies to the heater & controller
before proceeding.
For your own safety we recommend the use of
safety boots and leather faced gloves when
handling sharp or heavy items. The use of
protective eye wear is also recommended.
1.2 Model Definitions
VSOUT = AmbiRad Vision U Tube Unitary
heater with painted induced burner, ID Fan,
aluminised steel reflectors, end caps,
insulation, tube over shields, painted canopies
and optional end covers.
VSOUH = AmbiRad Vision U Tube
Herringbone heater with painted induced
burner, Damper, aluminised steel reflectors,
end caps, insulation, tube over shields, painted
canopies and optional end covers.
VSXO = AmbiRad Vision High efficiency
U Tube heater with forced burner, recuperative
heat exchanger, aluminised steel reflectors,
end caps, insulation, tube over shields, painted
canopies and optional end covers.
1.3 Heater Suspension
See fig 1.b. Attachment to the heater
support lugs should be made by a ‘speed
link’, D shackle or in the case of drop rods, a
closed formed hook. The hanging attachments
to overhead steelwork etc. must be purpose
made to good sound engineering practice or of
a proprietary type fixing. They must be
adequately fixed and designed to carry the
whole weight of the heater. In the event of
suitable roof steelwork being unavailable,
additional steelwork should be fitted to enable
vertical hangers to be used for suspending the
heaters.
If there are any doubts as to the strength or
suitability of roof steelwork to which heaters are
to be suspended, please refer to a Consultant,
Architect or owner of the building. The
minimum mounting heights for AmbiRad heaters
are given in the table below.
1.4 Wall Mounting
These radiant tube heaters can be wall mounted
using the appropriate bracket (AmbiRad part no
WMB-13-22-38).
When using the wall mounting brackets the
heater must be inclined at an angle between 30°
and 35°.
Table 1 Angle Mounting
U Tube
Heater
Size
Required
angle
Chain
length
Eyebolt
position
15 - 50
30-35°
12 links 1
1. Installation Requirements.
Isolate any electrical supply to the
heater and controller before proceeding.
The heater must be suspended by
ALL of the suspension brackets.
3
.
E
Figure 1.a. Angle Mounting using the Wall
mounting bracket
1
Model
MINIMUM
Mounting Height (m)
Horizontal
Inclined / wall
mounted
15
4.4 3.9
20
4.9 4.4
25
5.4 4.7
30
6.3 5.5
35
6.5 5.7
40
6.9 6.0
45
7.3 6.5
50
7.8 6.9