Service manual
SERVICING
52
Turn gas supply off. 
Set thermostat to call 
for heat. 
Smart Valve is 
powered. (24volt 
nominal- 19.5 volts 
minimum. 27.5 Max.
Igniter warms up and 
glows red.
Turn gas on. 
Pilot burner lights
Unplug pilot burner cable 
Measure voltage at Terminals 1&2 on 
Smart Valve. (19.5 Minimum 27.5 Max.)
Replace Igniter/Flame 
sensor assembly
Start
Check
Replace Smart Valve
YES
YES
Check line voltage
Check primary, Aux. & roll out limits
Check Voltage @ transformer
Check induced draft blower operation 
Correct line voltage
Correct low voltage
Reset or replace limit
Replace control board
NO
Check pilot to burner alignment.
Correct pilot position
Check igniter continuity with Ohm meter
SMART VALVE DIAGNOSTIC / TROUBLE SHOOTING CHART
PROCEDURE
ACTION
Measure voltage @ L1, L2, & GR.
Measure voltage @ Control board GY-25 
& R-1
Measure voltage @ Control board molex 
plug "OR-49 to BR-21.  Must read 0 volts
Check Voltage @ Red & Violet Wires to 
ID blower @ Control Board(230 volts)
Check thermostat & wiring
Measure voltage @ Control board 
terminals "W" to C 19.5 Min. 27.5 Max.
Repair/replace 
thermostat/thermostat 
wiring
Check gas valve
Check ingiter
Check gas valve
Check pilot assembly
NO
Verify that pilot is positioned in front of the 
burner carry-over
Verify that pilot orifice is free of 
obstructions and corectly sized for gas 
dd
Check pressure switch operation 
Check Voltage @ Yel.-11 at Smart valve 
(19.5 volts min. 27.5 Max.)
Replace I.D. Blower
Repair wiring or re- 
place pressure switch
YES
NO
Verify that pilot adjustment on gas valve 
open and adjusted correctly
Clear obstruction or 
replace pilot orifice
Open or adjust gas 
valve pilot 
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
NO