Service manual

SERVICING
25
Complaint No Cooling / Heating Unsatisfactory Clg / Htg
System
Operating
Pressures
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
SYMPTOM
System will not start
Compressor will not start - fan runs
Comp. and Cond. Fan will not start
Evaporator fan will not start
Condenser fan will not start
Compressor runs - goes off on overload
Compressor cycles on overload
System runs continuously - little clg / htg
Too cool and then too warm
Not cool enough on warm days
Certain areas to cool others to warm
Compressor is noisy
System run blows cold air (Heating)
Unit will not terminate defrost
Unit will not defrost
Low suction pressure
Low head pressure
High suction pressure
High head pressure
Test Method
Remedy
See Service Procedure Ref.
Power Failure
Test Voltage S-1
Blown Fuse
Imspect Fuse Size & Type S-4
Loose Connection
Inspect Connection - Tighten S-2
Shorted or Broken W ires
Test Circuits W ith Ohmmeter S-3
Open Overload
Test Continuity of Overload S-17A
Faulty Thermostat
Test continuity of Thermostat & W iring S-3
Faulty Transformer
Check control circuit with voltmeter S-4
Shorted or Open Capacitor
Test Capacitor S-15
Shorted or Grounded Compressor
Test Motor W indings S-17B
Compressor Stuck
Use Test Cord S-17C
Faulty Compressor Contactor
Test continuity of Coil & Contacts S-7, S-8
Faulty Fan Relay
Test continuity of Coil And Contacts S-7
Open Control Circuit
Test Control Circuit with Voltmeter S-4
Low Voltage
Test Voltage S-1
Faulty Evap. Fan Motor
Repair or Replace S-16
Shorted or Grounded Fan Motor
Test Motor W indings S-16
Improper Cooling Anticipator
Check resistance of Anticipator S-3
Shortage or Refrigerant
Test For Leaks, Add Refrigerant S-103
Restricted Liquid Line
Replace Restricted Part S-112
Dirty Air Filter
Inspect Filter-Clean or Replace
Dirty Indoor Coil
Inspect Coil - Clean
Not enough air across Indoor Coil
Speed Blower, Check Duct Static Press S-200
Too much air across Indoor Coil
Reduce Blower Speed S-200
Overcharge of Refrigerant
Release Part of Charge S-113
Dirty Outdoor Coil
Inspect Coil - Clean
Noncondensibles
Remove Charge, Evacuate, Recharge S-114
Recirculation of Condensing Air
Remove Obstruction to Air Flow
Infiltration of Outdoor Air
Check Windows, Doors, Vent Fans, Etc.
Improperly Located Thermostat
Relocate Thermostat
Air Flow Unbalanced
Readjust Air Volume Dampers
System Undersized
Refigure Cooling Load
Broken Internal Parts
Replace Compressor
Inefficient Compressor
Test Compressor Efficiency S-104
High Pressure Control Open
Reset And Test Control S-12
Unbalanced Power, 3PH
Test Voltage
W rong Type Expansion Valve
Replace Valve
Expansion Device Restricted
Replace Valve
Expansion Valve Bulb Loose
Tighten Bulb Bracket
Inoperative Expansion Valve
Check Valve Operation S-110
Loose Hold-down Bolts
Tighten Bolts
Faulty Reversing Relay
Test continuity of Coil And Contacts S-7
Faulty Defrost Relay
Test continuity of Coil And Contacts S-7
Faulty Reversing Valve
Test Valve Operation S-21
Leaking Check Valve/Orifice
Replace Check Valve
Faulty Defrost Timer
Test Timer Operation S-23/24
Faulty 30/60 Control
Test Control S-25
Additional Opt Elect. Heat Req.
Run Load Calculation, Add Heaters
Open fuse or limit in Elect. Htr
Inspect Fuses and Limits S-50
O.D. Thermostat setting to Low
Raise Setting
Clg or Htg Cycle
Heat Pump Cycle only
COOLING OR HEAT PUMP - SERVICE ANALYSIS GUIDE