Specifications

C/D - 9
Wall Sleeves
The wall sleeve must be industry accepted dimen-
sions: 13-3/4” depth x 42” width x 16-1/16” height and
constructed of insulated galvanized steel with electro-
deposition paint finish with ULV resistant high-solids
polyester overspray. Sleeve must be shipped with
weather resistant rear closure panel installed.
Outdoor Grilles
Must be architectural extruded, louvered aluminum
( AGK*** B) or standard stamped aluminum
(SGK**B). All other grilles must be submitted to PTAC
manufacturer for feasibility, airflow characteristics and
compliance with U.L. regulations, where necessary.
Remote Temperature Sensor (RTS02)
A field installed thermister will override the unit mounted
thermostat to allow more accurate, internal wall-sens-
ing of room ambient temperature. All other modes and
functions remain at the PTAC unit.
Condensate Drain Kit (DK9001)
Attaches to the bottom of the wall sleeve for directional
controlled internal or external disposal of condensate,
defrost, or rain water.
Subbase Kit (PTSB***C)
Necessary for U.L. listing requirements for 265 volt
units (Hard Wire Kit may be substituted for Subbase kit).
Optional for 230/208 volt units. Must be prewired to
facilitate field electrical connections and include a NEMA
6 or 7 configuration electrical receptacle. It must have
two leveling screws for sleeve support and accurate unit
leveling during installation. Locations for field installa-
tion of physical disconnect switches, cartridge-style
fuse holders and circuit breakers must be provided.
Side-skirts must be provided with subbases.
(PTSB000C Non-Electrical Subbase available.)
Power Vent & Damper
Must be provided to maximize ventilation air intake to up
to approximately 95 CFM. Power vent must be off and
damper door closed when unit fan is de-energized.
Fuse Holder (included in 265V chassis)
Must be installed either in the unit or the subbase and
must match the electrical requirements of the chassis.
Security Key Locks (KL03)
Must be installed to prevent tampering of the unit con-
trols. Unit room cabinet must also be secured to the
chassis with field supplied screws. U.L. approved for
institutional use only.
Disconnect Switch
Power disconnect switch must be installed in subbase
for use as a physical disconnect where required by local
codes.
Duct Kits ( MDK02, EDKO2, TDK02)
Three kits must be supplied to provide ducted condi-
tioned air into a second room: a main duct kit, an
extension duct kit, and a terminal duct kit.
Hydronic Heat Kit
Is required for heating functions instead of electric
resistance heaters. Unit must retain complete service
access with the kit installed. Proper water or steam
valves must be used.
Condensate Removal Pump (Heat Pumps only)
Must be installed to assist in removing the condensate
developed by the heat pump operation and transfer it to
the indoor coil to dissipate into the room adding humid-
ity to the room.
Circuit Breaker Kit
Must be installed in subbase to provide overcurrent
protection for proper 230/208 volt amperage. Can also
be used as a physical disconnect where local codes
permit for 230/208 voltage.
Hard Wire Kit
Must be used to permanently wire chassis for hard wire
purposes. (For 265 volt units, Hard Wire Kit may be
substituted with Subbase Kit.)
Charcoal Filter Kit (Optional)
Amana
®
brand Activated Charcoal filters absorb odors
caused by cigarette, pipe or cigar smoke & odors
caused by mold, mildew, etc. These replacement filters
are polyester fibers coated with actiated charcoal. Each
filter is individually wrapped to assure maximum ab-
sorption and durability when installed. (10 filters per kit.)
Thermostats
A manufacturer approved manual, auto changeover, or
programmable thermostat must be installed to provide
full remote operation of the chassis. A Remote Es-
cutcheon Kit must be used to indicate remote operation.
(The optional accessories listed below perform specific functions required in some installations.)
(New installations typically require a minimum of WS900B wall sleeve and an outdoor grille.)
GUIDE SPECIFICATIONS - Accessories