Instruction manual

8
gas, electrical, and drain trap and drain line connections. The com-
bustion and ventilating air openings in the front and top panels of the
furnace must never be obstructed. Refer to the unit Product Data
Bulletin for minimum clearances to combustible surfaces.
FURNACE SUSPENSION
If suspending the furnace from rafters or joist, use 3/8" threaded rod
and 2”x2”x3/8” angle iron as shown below. The length of rod will
depend on the application and the clearances necessary.
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL
3/8" DIAMETER
THREADED ROD
(6 PLACES)
PROVIDE 8" MINMUM C LEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BLOWER REMOVAL
ASSURE FURNACE IS LEVEL FROM
END TO END AND HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE
POSITION AS CLOSE AS POSSIBLE
TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMVOAL
HOLD DOWN
NUTS
SUPPORT
NUTS
2"x2"x3/8"
ANGLE IRON
(3 PLACES)
Figure 1 - Suspended Furnace
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting system
serving other appliances, the venting system may be too large to
properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American
National Standard/National Standard of Canada for Gas-Fired Cen-
tral Furnaces ANSI Z21.47-1998, CSA-2.3-M98 Section 1.23.1.
The following steps shall be followed with each appliance connected to the
venting system placed in operation, while any other appliances con-
nected to the venting system are not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal pitch, as
required by the National Fuel Gas Code, ANSI Z223.1 or the CAN/
CSA B149 Installation Codes and these instructions. Determine that
there is no blockage or restriction, leakage, corrosion and other de-
ficiencies which could cause an unsafe condition;
c. In so far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to the
venting system are located and other spaces of the building. Turn
on clothes dryers and any appliance not connected to the venting
system. Turn on any exhaust fans, such as range hoods and bath-
room exhausts, so they shall operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being inspected
in operation. Adjust thermostat so appliance shall operate continu-
ously;
e. Test for draft hood equipped appliance spillage at the draft hood
relief opening after 5 minutes of main burner operation. Use the
flame of a match or candle;
f. After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above, re-
turn doors, windows, exhaust fans, fireplace dampers and any other
gas burning appliance to their previous conditions of use;
g. If improper venting is observed during any of the above tests, the
common venting system must be corrected.
Corrections must be in accordance with the latest edition of
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or
CAN/CSA B149 Installation Codes.
If resizing is required on any portion of the venting system,
use the appropriate table in Appendix G in the latest edition of
the National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA
B149 Installation Codes.
THERMOSTAT LOCATION
In an area having good air circulation, locate the thermostat about
five feet high on a vibration-free inside wall. Do not install the
thermostat where it may be influenced by any of the following:
Drafts, or dead spots behind doors, in corners, or under
cabinets.
Hot or cold air from registers.
Radiant heat from the sun.
Light fixtures or other appliances.
Radiant heat from a fireplace.
Concealed hot or cold water pipes, or chimneys.
Unconditioned areas behind the thermostat, such as an
outside wall.
HOT
COLD
DRAFTS OR DEAD SPOTS
-BEHIND DOORS
-IN CORNERS
-UNDER CABINET S
Figure 2 - Thermostat Influences
Consult the instructions packaged with the thermostat for mount-
ing instructions and further precautions.
VV
VV
V
. CO. CO
. CO. CO
. CO
MBUSTIMBUSTI
MBUSTIMBUSTI
MBUSTI
OO
OO
O
N AND VENTILN AND VENTIL
N AND VENTILN AND VENTIL
N AND VENTIL
AA
AA
A
TITI
TITI
TI
OO
OO
O
N AIR REQUIREMENTSN AIR REQUIREMENTS
N AIR REQUIREMENTSN AIR REQUIREMENTS
N AIR REQUIREMENTS
WARNING
T
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, SUFFICIENT
FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF FLUE GASES MUST
BE SUPPLIED.
M
OST HOMES REQUIRE OUTSIDE AIR BE SUPPLIED INTO THE
FURNACE AREA.
Improved construction and additional insulation in buildings have
reduced heat loss by reducing air infiltration and escape around
doors and windows. These changes have helped in reducing heat-
ing/cooling costs but have created a problem supplying combus-
tion and ventilation air for gas fired and other fuel burning appli-
ances. Appliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or improper com-
bustion of gas-fired appliances, thereby exposing building occu-
pants to gas combustion products that could include carbon mon-
oxide.
If this furnace is to be installed in the same space with other gas
appliances, such as a water heater, ensure there is an adequate
supply of combustion and ventilation air for the other appliances.