Instruction manual

18
Horizontal vent/flue pipe terminations should be as shown
in the following figure. Refer to
Section IX, Vent/Flue Pipe
and Combustion Air Pipe - Termination Locations
for
details concerning location restrictions. A 2 3/8” diameter
wall penetration is required for 2” diameter pipe while a 3
1/2” diameter hole is required for 3” diameter pipe. To
secure the pipe passing through the wall and prohibit
damage to piping connections, a coupling should be in-
stalled on either side of the wall and solvent cemented to
a length of pipe connecting the two couplings. The length
of pipe should be the wall thickness plus the depth of the
socket fittings to be installed on the inside and outside of
the wall. The wall penetration should be sealed with
silicone caulking material.
MIN.
12"
FROM
WALL
12"
TO GROUND OR
HIGHEST ANTICIPATED
SNOW LEVEL
WALL
INSIDE
OUTSIDE
TEE
or
90°ELBOW
TURNED
DOWN
COUPLING
ELBOW OR
COUPLING
Horizontal Termination (Single Pipe)
12" MIN.
VENT/FLUE TEE
or
90° ELBOW TURNED
DOWN
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
Horizontal Termination (Single Pipe)
Above Highest Anticipated Snow Level
In a basement installation, the vent/flue pipe can be run
between joist spaces. If the vent pipe must go below a joist
and then up into the last joist space to penetrate the
header, two 45° elbows should be used to reach the
header rather than two 90° elbows.
DIRECT VENT (DUAL PIPE) PIPING
Direct vent
installations require both a combustion air
intake and a vent/flue pipe. The pipes may be run horizon-
tally and exit through the side of the building or run
vertically and exit through the roof of the building. The
pipes may be run through an existing
unused
chimney;
however, they must extend a minimum of 12 inches above
the top of the chimney. The space between the pipes and
the chimney must be closed with a weather tight, corrosion
resistant flashing. Both the combustion air intake and a
vent/flue pipe terminations must be in the same atmo-
spheric pressure zone. Refer to
Section IX, Vent/Flue and
Combustion Air Pipe - Termination Locations or Concen-
tric Vent Termination
for specific details on termination
construction. For details concerning connection of pipes to
the furnace, refer to the
Section IX, Vent/Flue Pipe and
Combustion Pipe - Standard Furnace Connections or
Alternate Furnace Connections.
Vent/Flue and Combustion Air Pipe Lengths and
Diameters
Refer to the following table for applicable length, elbows,
and pipe diameter for construction of the vent/flue and
combustion air intake pipe systems of a direct vent (dual
pipe) installation. The number of elbows tabulated repre-
sents the number of elbows and/or tees in each (Vent/Flue
& Combustion Air Intake) pipe. Elbows and/or tees used
in the terminations must be included when determining the
number of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a
finished ceiling or other area where dripping of condensate
will be objectionable, insulation of the combustion air pipe
may be required. Use 1/2” thick closed cell foam insulation
such as Armaflex or Insultube where required.
2345678
Standard 2 68 65 62 59 56 53 50
Alternate 2 55 52 49 59 56 53 50
Standard 2 68 65 62 46 43 40 37
Alternate 2 55 52 49 46 43 40 37
Standard 2 55 52 49 46 43 40 37
Alternate 2 42 39 36 46 43 40 37
Standard 2 26 23 20
Alternate 2 7 10
Standard 3 88 84 80 76 72 68 64
Alternate 3 74 70 66 62 58 54 50
45,000
115,000
Number of Elbows
(1)(2)(3)
Not Recommended
Not Recommended
Unit
Input
(Btu)
Vent/Flue/Air
Intake
Termination
Pipe
Size
(in.)
Direct Vent (Dual Pipe)
Maximum Allowable Len
g
th of Vent/Flue & Combustion
Air Intake Pipe
(
ft
)
115,000
90,000
70,000
(1)
Elbows and/or Tees used in the terminations must be included when
determining the number of elbows in the piping system.
(2)
Number of elbows tabulated are for each (Vent/Flue & Combustion air
intake) pipe.
(3)
Minimum length of each Vent/Flue & Combustion Air Intake pipe is five
feet and one elbow/tee.
Vent/Flue and Combustion Air Pipe Terminations
The vent/flue and combustion air pipes may terminate
vertically, as through a roof, or horizontally, as through an
outside wall.
Vertical pipe terminations should be as shown in the
following figure.
Refer to Section IX, Vent/Flue Pipe and
Combustion Pipe - Termination Locations
for details con-
cerning location restrictions. The penetrations through the
roof must be sealed tight with proper flashing such as is
used with a plastic plumbing vent.