Specifications
Specifi cation Sheet
www.amana-ptac.com
4
Voltage
Electric
Heater
Size (kW)
No. of
Stages
Nominal Heating
Total Watts
6
Total Amps
8
Minimum
Circuit
Ampacity
2
Overcurrent
Protection
4
Power Cord
BTUH
@ 230V
BTUH
@ 208V
BTUH
@ 265V
230/208V 2.5/2.0 1 8,500 6,800 - - 2,650/2,140 11.5/10.2 14.2 15 6 - 15 P
230/208V 3.5/2.9 1 12,000 9,900 - - 3,650/3,040 15.8/14.5 19.6 20 6 - 20 P
230/208V 5.0/4.1 1* 17,100 14,000 - - 5,150/4,240 22.3/20.3 27.7 30 6 - 30 P
265V 2.5 1 - - - - 8,500 2,650 10.0 12.4 15 7 - 20 P
265V 3.7 1 - - - - 12,600 3,850 14.6 18.1 20 7 - 20 P
265V 5.0 1* - - - - 17,100 5,150 19.5 24.2 25 7 - 30 P
PTC and PTH Models—Electric Heater Performance
(Primary Heating for PTC Models; Auxiliary Heating for PTH Models)
These models are shipped without a chassis front or
electric heat, and they have an additional re lay and
40VA trans form er for water or steam valve operation.
Also avail able is Hydronic with Powered Vent and
Hy dron ic with Pow ered Door. See Model Nomenclature
for Spe cial Fea ture Codes for these models. See page
7 for hydronic ac ces so ries.
NOTES:
1. All 265v models must use our subbase (PTSB4**E) or an Amana
®
brand hard wire kit (PTPWHWK4)
2. Minimum branch circuit ampacity ratings conform to the Na tion al Electric Code. However, local codes should apply.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included and
factory-installed on Amana
®
brand all 265 volt chassis).
5. Heating capacity and effi ciency is based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24 °F outdoor
ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09*B**AE.
7. Please specify 2-digit heater kW size to complete model number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09*B*AE.
9. Refrigerant used in all systems is R-22.
10. All units meet or exceed ASHRAE 90.1 standards.
11. All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
PTC Model Specifi cations—Cooling/Electric Heat
*Approximately 95 CFM with optional power vent kit. Actual vent CFM performance will vary due to application and installation conditions.
See page 11 for Power
Cord Confi guration
Hydronic Heat Models
Hydronic Models/Hot Water & Steam Heating
Hydronic with Manual Door
Model Number Voltage Capacity Cooling Capacity EER
PTC093B00HE 230/208 9,100/8,900 11.6
PTC123B00HE 230/208 12,000/11,900 10.8
PTC153B00HE 230/208 14,200/14,000 9.5
PTC094B00HE 265 9,100 11.6
PTC124B00HE 265 12,200 10.8
PTC154B00HE 265 14,200 9.5
*PTH/PTC09*B50*E/J has the same air fl ow as a PTC/PTH12*B***E/J. (Not available on 7,000 BTU models.)
Model
1, 7, 9, 10
PTC073B**AJ PTC074B**AE PTC093B**AJ PTC094B**AE PTC123B**AJ PTC124B**AE PTC153B**AJ PTC154B**AE
Voltage
1, 3, 11
230/208 265 230/208 265 230/208 265 230/208 265
Capacity (BTUH) 7,100/6,900 7,100 9,100/8,900 9,100
12,000/11,900
12,000
14,000/13,900
14,000
Amps 2.8/3.0 2.3 3.7/3.8 3.0 4.6/5.0 4.3 6.3/6.9 5.9
Watts 610/595 610 790/775 790 1,110/1,100 1,130 1,470/1,450 1,470
EER 11.6 11.6 11.5 11.5 10.8 10.8 9.5 9.5
Unit without Electric Heater
Min. Circuit Ampacity
2, 4
4.0 3.6 5.1 4.4 6.4 5.7 8.8 7.7
CFM
(Cool/Wet Coil)
High
Low
245/240
220/205
245
220
245/240
220/205
245
220
325/315
250/229
325
250
325/315
250/220
325
250
CFM
(Dry Coil)
High
Low
265/260
230/215
265
230
265/260
230/215
265
230
345/335
265/235
345
265
345/335
265/235
345
265
Ventilated Air, CFM
(Fan Only)*
65* 65* 65* 65* 70* 70* 70* 70*
Ventilated Air, CFM
(Compressor & Fan)*
65* 65* 65* 65* 70* 70* 70* 70*
Dehumidifi cation
(Pints/Hr.)
1.6 1.6 2.6 2.6 3.5 3.5 4.4 4.4
Net Weight (lbs.) 90 90 95 95 105 105 110 110
Shipping Weight (lbs.) 105 105 110 110 120 120 125 125