Specifications
Specifi cation Sheet
www.amana-ptac.com
11
Mounting
Holes
(Drilled by
Installer)
Plastic
Anchor
Screws
Expansion
Anchor Bolt
Toggle Bolt
Wood Screw
Alternative
Fastening Method
(Field Supplied)
FINISHED FLOOR
42 1/4"
16 1/4"
MIN
MAIN STUD
JACK STUDS
HEADER - 4" x 4" OR
DOUBLE 2"x 4" ON EDGE
SUB-FLOOR
CRIPPLE
JACK STUD
ADJUST FRAMING TO
SECURE THIS DIMENSION
Framing for Accessory Wall Sleeve (WS900D)
FASTENING WALL SLEEVE
When installed in an opening, the Wall Sleeve
must be hor i zon tal ly level (side-to-side) and
pitched ¼ bubble to the outside. (NOTE: To ensure
unit’s maximum effi ciency, DO NOT over- or under-
pitch.)
Wall Sleeve must
extend a minimum of
¼” beyond outside
wall to allow for proper
caulking.
Wall Sleeve Opening Height
Should Be Squared with
Wall Sleeve Opening Width
H = 16¼"
W = 42¼"
INSTALLATION NOTES
1. If Subbase (PTSB***E) is installed, allow minimum
3¼” height clearance and maximum 5” height
clearance between wall sleeve and fl oor; allow
minimum 2¾” protrusion from a fi nished wall. See
Note 4 if using hydronic units.
2. Drain Kit (DK900D) shipped separately. Can be
mounted either right side, left side or bottom of
sleeve. If mounted to bottom of sleeve, allow 2”
height clearance from fl oor to bottom of sleeve.
3. For U.L. approval, 265V units must use Amana
®
brand Subbase (PTSB***E) or Amana
®
brand Hard
Wire Kit (PTPWHWK4). Overcurrent protection on
265V units must be by cartridge-style time delay
fuses, which are included and factory-installed on
the Amana
®
brand 265V chassis.
4. If Hydronic Kit (HWK03 or HVK03) is installed, Wall
Sleeve must extend exactly 3" into the room from
the fi nished interior wall. If using the Amana
®
brand Subbase (PTSB***E), only the minimum 3¼”
height clearance between wall sleeve and fl oor is
permissible.
5. If Duct Kit (MDK02B) is installed, allow a minimum of
2⅜” into the room from the fi nished interior wall.
Power Receptacle Confi guration
NEMA6-30R; 250V receptacle,
used on 230/208V units
G
NEMA7-30R; 277V receptacle,
used on 265V units
G
NEMA6-15R; 250V receptacle,
used on 230/208V units
G
NEMA6-20R; 250V receptacle,
used on 230/208V units
G
W
NEMA7-20R; 277V receptacle,
used on 265V units
G
277V Rating Power Cord Plugs
NEMA 7 Confi guration
G
W
20 amp
G
W
30 amp
250V Rating Power Cord Plugs with LCDI Device
NEMA 6 Confi guration
Power Cord Plugs
15 amp
20 amp
30 amp
All units come with factory-installed power cords.
All units less than 250 volts come with LCDI device.