Specifications

32
PROPER INSTALLATION
CONFIGURATION SETTINGS
---
Start Configurati on position
Interface Usage 0*
Unit is only controlled by the PTAC touchpad.
rE Unit is both controlled by a wireless thermostat and/or the touchpad.
L5 Unit is controlled by a wired thermostat via the low voltage terminals only.
Au*
The fan only runs with the call for heating or cooling.
On
The fan runs continuously except in the OFF position.
C
The fan runs continuously in cooling and cycles with call for heating.
bP
Unit is equipped with fan operation button for guest selection of fan cycling.
bA
Unit is equipped with fan operation button, but self reverts to cyclic fan.
bC
Unit is equipped with fan operation button, but self reverts to continuous fan.
A
The fan always runs even in OFF mode
C
Cooler only with or without electric heat.
H*
Heat Pump.
0
Service no Operation "Eo"
C4
Room Identification first two digits
00-99
Set first two digits of room identification
C5
Room Identification last two digits 00-99
Set last two digits of room identification
0*
"No Occupancy" detection devices
1
Wired Door Switch and Motion Sensor present
18 Enter "No Occupancy" routine 18 hours after last control selection
0*
Normally Closed Device (Open when sensing motion)
1
Normally Open Device (Closed when sensing motion)
C8 Cooling Temperature Limiting
60*-72
Select temperature between 60 and 72 for minimum cooling set point
C9 Heating Temperature Limiting
68-90, 80*
Select temperature between 68 and 90 for maximum heating set point
8*
Mating thermostat has a "B" terminal
0
Mating thermostat has an "O" terminal
0*
Not Active
A
Active
c3 Unrented Cooling Temperature
45-95, 79*
Select temperature between 45 and 95 minimum unrented cooling set point.
c4 Unrented Heating Temperature
45-95, 63*
Select temperature between 45 and 95 minimum unrented heating set po int.
0*
Not Active
1
Active
U
Active in No occupancy / Unrented State
CC Dehumidistat call for a drop in temperature
3-8
3-8
F*
Fahrenheit Scale
C
Celsius Scale
L*
On, low fan*
H
On, high fan
0
Off
CF Hi. Speed Cooling Smart Temperature
5*-9
5-9
CH Hi Speed Heating Smart Temperature
6-8*
6-8
CJ 2nd S tage Heat. Dif. 4*-8
4-8
--
No electric heat
d1 Room Air Mix Cooling 1*
On
0
Off
d2 Room Air Mix Heating 0*
Off
1
On
d3 Air Mix Fan Speed L*
Low
H
Hi
gh
d4 Heating Smart Speed 0
Not Available
1*
Available
d5 Warnings, 1*
Enabled
OCT Lock & LE D
0
Dis-enabled
d6 Sensorless Un-Occ. Time and Fan Revert Time 1-32
1- 32, 18*
d7 1st Un-Occ. Set Back Temperature 1-16
1-16, 2*
d8 1st Un-Occ. Set Back Time .1, .5, 1-24
.1, .5, 1-24, .5*
d9 2nd Un-Occ. Set Back Temperature 1-16
1-16, 3*
dA 2nd Un-Occ. Set Back Time .1, .5, 1-24
(d8)-24, 1*
dB 3rd Un-Occ. Set Back Temperature 1-16
1-16, 6*
dC 3rd Un-Occ. Set Back Time .1, .5, 1-24
(dA)-24, 3*
dH Electric Heater Size
00*, 15, 20,
25, 35, 50
00*, 15, 20, 25, 35 & 50
r4 Room Prefix 00* - 99
00* - 99
r5 Room Suffix 00* - 99
00* - 99
*Indicates factory default.
Reverse Cycle "B" or "O"
selection for thermostat
Description
C1
C2 Fan Operation
Wired Unrented Set Backc2
Option CodeFeature Code
C0
DehumidificationCb
Description
C6 Wired Occupancy
C7 Wired Motion Sensor Type
C3 Reverse Cycle Operation
Cd English/Metric Temperature
CE Freeze Protection