Specifications
14
SPECIFICATIONS
NOTES:
1. All 265V models must use Amana
®
brand’s subbase (PTSB4**E) or an Amana
®
brand hard wire kit (PTPWHWK4).
2. Minimum circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts.
3. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent prote ction for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses
(included and factory installed on Amana
®
brand all 265 volt chassis). See heater performance for total MCA.
5. Heating capacity and efficiency are based on unit operation without condensate pump. Unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09
7. Please specify 2-digit heater kW size to complete model serial number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09
9. Re friger ant us ed in all sys tems i s R-22 .
10. All units meet or exceed ASHRAE 90.1 standards..
11. A l l u n i t s l e s s t h a n 2 5 0 v o l t s h a v e a L e a k C u r r e n t D e t e c t o r I n t e r r u p t e r ( L C D I ) p o w e r c o r d a n d m e e a t U L 4 8 4 s t a n d a r d s .
12. Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.
PTH********[M/R/Z]
PTH
073D***[ R/Z]
PTH
093D**AR
PTH
123C**AM
PTH
123D**AR
PTH
094D****
PTH
124C**AM
3.5/3.5 4.4/4.4 4.8 /5 .2 5.4/5.4 3.6 4.7
550/530 760/740 1,010/960 1,035/1,015 750 1,010
6,200/6,000 8,3 00/8,100 10,00 0/9,50 0 10,600/10,400 8,200 10,000
3.2/3.3 3. 2 2.9 3.0 3.2 2.9
--- --- --- --- --- ---
240/235 240/23 5 240/235 335 /325 240 230
Outdoor
Ambient
ºF
Heating BTUH
Note 5
Heating BTUH
Note 5
Heating BTUH
Note 5
Heat ing BTUH
Note 5
Heating BTUH
Note 5
Heating BTUH
Note 5
62 7,20 0/7,000 9,9 00/9,700 12,200/11,700 12,800/12,600 9,800 12,2 00
57 6,90 0/6,700 9,4 00/9,200 11,500/11,000 12,100/11,900 9,300 11,5 00
52 6,50 0/6,300 8,8 00/8,600 10,800/10,300 11,400/11,200 8,700 10,8 00
47 6,20 0/6,000 8,3 00/8,100 10,00 0/9,50 0 10,600/10,400 8,200 10,000
Rating
Point
(COP)*
ºF
3.2/3.3 3 2.9 3 3.2 2.9
42 5,900/5,700 7,800/7,600 9,300/8,800 9,900/9,700 7,700 9,300
37 5,600/5,400 7,300/7,100 8,600/8,100 9,200/9,000 7,200 8,600
32 5,300/5,100 6,800/6,600 7,800/7,300 8,400/8,200 6,700 7,800
27 5,000/4,800 6,300/6,100 7,100/6,600 7,700/7,500 6,200 7,100
24 4,800/4,600 6,000/5,800 6,700/6,200 7,300/7,100 5,700 6,700
Outdoor
Ambient
ºF
Watts Watts Watts Watts Watts Watts
62 °F 585/570 820/800 1,110/1,065 1,135/1,110 810 1,110
57 °F 575/555 810/790 1,080/1,030 1,105/1,085 800 1,080
52 °F 560/545 785/765 1,050/1,000 1,075/1,055 775 1,050
47 °F 550/530 760/740 1,010/960 1,035/1,015 750 1,010
42 °F 540/525 740/720 975/925 1,000/980 730 975
37 °F 530/515 715/695 940/890 965 /945 705 940
32 °F 515/500 700/680 890/840 915 /895 690 890
27 °F 505/490 670/650 945/795 870 /850 670 945
24 °F 500/485 650/630 900/770 845 /825 650 900
BTUH
5
N Models
CFM (Dry)
*COP = Coefficiency of Performance; per AHRI Test Procedures, units are rated for capacities and efficiencies.
COP
5
M Models
Heat ing Capacity
Reverse Cycle
1
Amps
12
Watts
12
HEATING PERFORMANCE - REVERSE CYCLE
230V 2 08V 265V
230/208 2.5/2.0 1 8,500 6,800 --- 2,650/2,140 11.6 / 10.5 14.5 15 6 - 15 P
230/208 3.5/2.9 1 12,000 9,900 --- 3,650/3,040 15.9/14.5 19.9 20 6 - 20 P
230/208 5.0/4.1 1* 17,100 14,000 --- 5,150/4,240 22.4/20.4 28.1 30 6 -30 P
265
2.5 1 --- --- 8,500 2,650 10.1 12.7 15 7 - 20 P
265 3.7 1 --- --- 12,600 3,850 14.7 18.3 20 7 - 20 P
265 5.0 1* --- --- 17,100 5,150 19.6 24.5 25 7 - 30 P
* PTH/PTC09*B50*G/K have the same airflow as a PTC/P TH12*B***G (not available on 7,0 00 BTU/h models).
HEAT PERFORMANCE (ELECTRIC HEAT) ELECTRIC DATA
(ALL BTUH S IZE S, ALL MODELS)
Nominal Heating
(BTUH)
Number
of
Stages
Electric Heater S ize
(kW)
Voltage
To tal
Watts
To tal
Amps
Minimum
Ampacity
1
Overcurrent
Protection
5
Power
Cor d
1