Specifications
12
SPECIFICATIONS
1. All 265V models must use Amana
®
brand’s subbase (PTSB4**E) or an Amana
®
brand hard wire kit (PTPWHWK4).
2. Minimum circuit ampacity ratings conform to the National Electric Code.
However, local codes should apply. Minimum voltage on 230/208 volt models is
197 volts; maximum is 253 volts.
3. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcu rrent p rotecti on for all units without electric heaters is 15 amps.
Overcurrent protection on 265 volt models must be cartridge-style time delay
fuses (included and factory installed on Amana
®
brand all 265 volt chassis).
See heater performance for total MCA.
5. Heating capacity and efficiency are based on unit operation without condensate
pump. Unit automatically switches to electric heat at approximately 24°F
outdoor ambient.
6. Total watts for 12,000 and 15,000 Btuh models. Subtract 70 watts for PT07/09
7. Please specify 2-digit heater kW size to complete model serial number.
8. Total amps for 12,000 and 15,000 Btuh models; subtract 0.2 amps for PT07/09
9. Refrigerant used in all systems is R-22.
10. All units meet or exceed ASHRAE 90.1 standards..
11 . A l l u n i t s l e s s t h a n 2 5 0 v o l t s h a v e a L e a k C u r r e n t D e t e c t o r I n t e r r u p t e r ( L C D I )
power cord and meeat UL 484 standards.
12. Refer to electric heat performance data for total MCA and recommended
overcurrent protection. Amps and Watts notation refers to compressor models
only.
PTC****A*
*Approximately 95 CFM with optional power vent kit. Actual vent
CFM performance will vary due to application and installation
conditions.
NOTES:
Model
1, 7 , 9 , 10 , 12
PTC
094D****
PTC
124C**AM
PTC
154D****
Voltage
1 , 3, 1 1
265 265 265
Capacity (BUTH)
9100 11,600 14000
Am p s
3.6
4.7
6.1
Watts
790
1,055
1458
EER
11.5 11.0 9.6
UNIT WITHOUT
ELECTRIC HEATER
Minimum Circuit Ampacity
2, 4, 12
4.4 5.8 7.5
CFM
HIGH 220 225 210
LOW 195 200 240
HIGH 240 230 335
LOW 210 200 260
FAN ONLY* 65* 65* 70
COMPRESSOR & FAN* 65* 65* 70
Dehumidification
(pints/hr)
2.6 3.3 4.4
Net Weight
95 105 110
Shipping Weight
(approx. lbs.)
110 120 125
COOLING DATA (COOLING with ELECTRIC HEAT)
Cool, Wet Coil
Dry Coil
Ventilated Air
Model
1, 7 , 9 , 10 , 12
PTC
073D**AR
PTC
093D**AR
PTC
123C**AM
PTC
123D**AR
PTC
133D**AR
PTC
153D**AR
Voltage
1 , 3, 1 1
230 / 208 230 / 208 230 / 208 230 / 208 230 / 208 230 / 208
Capacity (BUTH)
7,200/7,000 9 ,100 / 8,900 11,7 00 / 11,600 12,000 / 1 1,800 13,300 / 13,20 0 14,000/13,8 00
Am p s
3.5/3.5 4.4/4.4 4.8/5.2 5.4/5.4
5.9/6.4
6.7/6.7
Watts
625/600 790 / 775 1,070,/,1,040 1,120,/,1,100
1265/1235
1445/1420
EER
11.5/11.7 11.5 11.0/11.2 10.7 10.5/10.7 9.7
UNIT WITHOUT
ELECTRI C HEATER
Minimum Circui t Ampacity
2, 4, 12
4.2 5.4 6.4 6.6 7.8 8.2
CFM
HIGH 220/215 220/215 220/215 310/300 310/300 310/300
LOW 195/190 19 5/190 195/190 24 0/230 240/230 240/230
HIGH 240/235 240/235 240/235 335/325 335/325 335/325
LOW 210/205 21 0/205 210/205 26 0/250 260/250 260/250
FAN ONLY* 65* 65* 65 * 70* 70* 70*
COMPRESSOR & FAN* 65* 65* 65 * 70 * 70* 70*
Dehumidification
(pint s/hr)
1.6 2.6 3.3 3.3 3.3 4.4
Net Weight
90 95 105 105 105 110
Shipping We ight
(approx. lbs.)
105 110 120 120 120 125
Cool, Wet Coil
Dry Coil
Ventilated Air
COOLING DATA (COOLING with ELECTRIC HEAT)